I/O Number; Concept Of I/O Number Assignment - Mitsubishi L02CPU User Manual

Melsec-l series
Hide thumbs Also See for L02CPU:
Table of Contents

Advertisement

2.2

I/O Number

This section describes the I/O number assignment required for data communication between the CPU module or its
built-in functions and I/O modules or intelligent function modules.
2.2.1

Concept of I/O number assignment

(1) Purpose of I/O number assignment
I/O numbers can be assigned with any given number for the following purposes.
(a) Reserving points for future module changes
The number of points can be reserved to prevent the I/O number modification when the current module is
changed in the future to the one with the different number of occupied I/O points.
(b) Preventing I/O numbers from being changed
The change in the I/O numbers can be prevented when an I/O module or intelligent function module, whose
occupied I/O points are other than 16, is removed due to failure.
(c) Changing the I/O numbers to those used in the program
When the I/O numbers used in the actual system differ from those in the program, the I/O numbers of each
module can be changed to the ones in the program. If any of the I/O modules whose number of I/O points are
other than 16 fails without I/O assignment setting, the I/O numbers assigned following to the failed module may
change, leading to a malfunction. For this reason, making the I/O assignment setting is recommended.
(2) I/O number assignment
The I/O numbers are represented in hexadecimal. The following is an example of an I/O number assignment to
the L26CPU-BT.
The start I/O numbers are as below.
Built-in I/O
Built-in CC-Link
The module on the right side of a CPU module
I/O number assignment is not necessary for the built-in Ethernet port, RS-232, and END cover.
Power
CPU module
Input
supply
(built-in I/O
module
module
and
built-in CC-Link)
points
0000
0030
to
003F
002F
Target
CHAPTER 2 APPLICATION OF PROGRAMMING
Intelligent
Input
Output
function
module
module
module
16
32
16
16
points
points
points
0040
0060
0070
to
to
to
to
005F
006F
007F
L02CPU
Default
I/O assignment
0000
Change allowed
H
0010
Change allowed
H
L26CPU-BT
Default
I/O assignment
0000
Change allowed
H
0010
Change allowed
H
0030
Change allowed
H
39
2