(b) Accuracy
The value obtained by the END instruction is added to the current value when the OUT T
instruction is executed. The current value is not updated while the timer coil is off even if the OUT T
ST
instruction is executed.
[Program example]
[Current value update timing]
OUT T0
END
processing
Program
ON
OFF
External input
to X0
OFF
CPU module's
X0
OFF
Coil of T0
OFF
Contact of T0
1
2
10ms counting
Count with END
instruction
Current value
of T0
Accuracy of the timer response that is from reading input (X) to output the data are up to
"2-scan time + timer limit setting".
OUT T0
OUT T0
OUT T0
END
END
processing
processing
ON
ON
1
2
3
1
2
1
2
3
2
0 + 2 = 2
2 + 3 = 5
Accuracy from timer coil on to contact on
- (1 scan time + timer limit setting) to (1 scan time)
On timing for coil of the timer
Input reading timing
OUT T0
OUT T0
END
END
END
processing
processing
processing
ON
2
3
1
2
1
2
3
3
2
7 + 3 = 10
5 + 2 = 7
CHAPTER 5 DEVICES
or OUT ST
or OUT
3
241
5