5.4

Module Access Devices

5.4.1

Intelligent function module device

The intelligent function module device allows direct access from the CPU module to the buffer memories of the
connected intelligent function modules.
(1) Specification method
Specify the I/O number and buffer memory address of the intelligent function module.
Specification method:
(2) Application example
When the L60AD4 high-speed analog-digital converter module is connected in the position of the start I/O number
X/Y050, specify the device as shown below to store digital output values of CH.1 to CH.4 into D0 to D3
accordingly.
If the intelligent function module device is used, device comments can be attached to the buffer memory.
Operating manual for the programming tool used
U
\G
Buffer memory address (setting range: 0 to 65535 in decimal)
Start I/O number of intelligent function module
Setting: First 2 digits of start I/O number expressed with 3 digits
X/Y1F0
Setting range: 00
to FF
H
X/Y1F0
Specification: 1F
H
L60AD4
11
CH1 Digital output value
12
CH2 Digital output value
13
CH3 Digital output value
14
CH4 Digital output value