Mitsubishi L02CPU User Manual page 289

Melsec-l series
Hide thumbs Also See for L02CPU:
Table of Contents

Advertisement

(2) PLC System Setting
Parameters of the system required for use of the CPU module are set.
Parameter
Item
Low Speed
Timer Limit
Setting
Low Speed
RUN
RUN-PAUSE
Contacts
*1
PAUSE
Latch Data Backup Operation
Valid Contact
Remote Reset
Output Mode at STOP to RUN
Intelligent Function Module
Setting (Interrupt Pointer
Setting)
Description
No.
Set the time limit for the low
1000
H
speed timer or high speed timer.
Set the contacts that control
1001
RUN PAUSE of the CPU
H
module.
Set the valid contact device No.
1014
used for backup of latch data to
H
the standard ROM.
Select whether to allow the
1002
H
remote reset.
Set the status of the outputs (Y)
1003
when the operating status is
H
switched from STOP to RUN.
Assign the interrupt pointers (I50
to I255) and set the start I/O
100A
H
number and start SI number of
each intelligent function module.
Setting range
1ms to 1000ms (in increments of
100ms
1ms)
0.01ms to 100.0ms (in
10ms
increments of 0.01ms)
X0 to X1FFF
X, M, B
Selected/deselected
Deselected
Previous state, Recalculate
The previous
(output is 1 scan later)
state
• Start I/O No.
L02CPU: 0 to 3D0
L26CPU-BT: 0 to FF0
• Start SI No.
50 to 255
APPENDICES
Default
Reference
Page 238,
Section 5.2.10
Page 106,
Section 3.13
Page 159,
Section 3.27
Page 106,
Section 3.13
Page 93,
Section 3.7
Page 273,
Section 5.10
(To the next page)
287
APPEN
DIX