Mitsubishi L02CPU User Manual page 121

Melsec-l series
Hide thumbs Also See for L02CPU:
Table of Contents

Advertisement

(d) Forced on/off timing
Refresh area
• Input and output used in the built-in I/O
function.
• Input and output of modules connected
Input and output of the CPU module to be
refreshed from RX/RY of a CC-Link module
(e) Number of registerable devices
Up to 32 devices in total can be registered.
(f) Checking the execution status
• Reading the forced on/off registration status of a programming tool.
• Flashing of the MODE LED (green) (The MODE LED flashes in green when a device is registered.)
• The on status of the 1st bit in SD840 (Debug function usage).
When checking by the MODE LED or SD840, remind that they are also used to check the execution status of executional
conditioned device tests. (
(g) Forcibly turning on/off from multiple programming tools
Forced on/off can be registered to a single CPU module from multiple programming tools. In this case, the last
registration is effective. For this reason, the forced on/off status which is different from the status actually
registered in the CPU module may be displayed on the screen that registered forced on/off earlier. When the
forced on/off registration is performed from multiple programming tools, click the
update the data, and execute the function.
(h) Status of devices after forced on/off registration data are canceled
Forced on/off registered device
• Input used in the built-in I/O function
• Input from connected modules on the base unit
Input of the CPU module to be refreshed from RX
Input
of a CC-Link module
Output other than above (outside of the refresh
range)
• Output used in the built-in I/O function.
• Output from connected modules on the base
unit.
Output
Output of the CPU module to be refreshed from
RY of a CC-Link module
Output other than above (outside of the refresh
range)
• During END processing (input refresh)
• At execution of the COM instruction (input refresh)
• At execution of an instruction using direct access input (DX) and direct access output
(DY)
• At execution of the RFS or MTR instruction
• At execution of an instruction used for a system
• During END processing (auto refresh)
• At execution of the COM instruction (auto refresh)
• At execution of the ZCOM instruction (auto refresh)
Page 121, Section 3.19)
Program operations (on/off)
performed
Uses the on/off status input from modules.
Uses the on/off status refreshed via CC-Link.
Uses the results of program operations.
Outputs the results of program operations.
Outputs the results of program operations. (The
results are not output externally.)
CHAPTER 3 CPU MODULE FUNCTIONS
Timing
button to
Program operations (on/off) not
performed
Holds the forced on/off status.
Holds the registered on/off status.
Holds the forced on/off status.
3
119