(4) PLC RAS Setting
Parameters required for performing the RAS functions are set.
Item
WDT Setting
WDT (Watchdog
Timer) Setting
Initial Execution
Monitoring Time
Error Check
Operating Mode When There is an Error
290
Parameter
Description
No.
Set a watchdog timer value.
3000
H
Set a watchdog timer value for
using an initial execution type
program.
Whether to check the following
errors can be selected.
3001
• Carry Out Battery Check
H
• Check Device Range at
Indexing
Set the operation mode of the
CPU module when the following
errors are detected.
• Computation Error
3002
H
• Intelligent Module Program
Execution Error
• File Access Error
• Memory Card Operation Error
Setting range
Default
10ms to 2000ms
(In increments of
200ms
10ms)
10ms to 2000ms
(In increments of
10ms)
Selected/
Selected
deselected
Stop/Continue
Stop
Reference
Page 82,
Section 3.3
Page 60,
Section 2.8.1
Page 150,
Section 3.24
Page 150,
Section 3.24