FX
-20SSC-H Positioning Block User's Manual
3U
BFM number
X axis
Y axis
BFM #523
Control command
Manual pulse input
BFM
BFM
magnification
#525,#524
#625,#624
(numerator)
Manual pulse input
BFM
BFM
magnification
#527,#526
#627,#626
(denominator)
*1.
For details on the user units, refer to the section given below.
Item
Description/Setting range
b0
Stores positioning parameters of X axis (BFM#14000 to
BFM #14199) to flash memory
b1
Stores positioning parameters of Y axis(BFM#14200 to
BFM #14399) to flash memory
b2
Stores table information of X axis (BFM #1000 to
BFM #3999) to flash memory
b3
Stores table information of Y axis (BFM #4000 to
BFM #6999) to flash memory
b4
Stores table information of XY axes (BFM #7000 to
BFM #12999) to flash memory
b5
Stores servo parameters of X axis (BFM #15000 to
BFM #15199) to flash memory
b6
Stores servo parameters of Y axis (BFM #15200 to
BFM #15399) to flash memory
b7
Not available
b8
Initializes positioning parameters of X axis (BFM #14000 to
BFM #14199)
b9
Initializes positioning parameters of Y axis (BFM #14200 to
BFM #14399)
b10 Initializes table information of X axis (BFM #1000 to
BFM #3999)
b11 Initializes table information of Y axis (BFM #4000 to
BFM #6999)
b12 Initializes table information of XY axes (BFM #7000 to
BFM #12999)
b13 Initializes servo parameters of X axis (BFM #15000 to
BFM #15199)
b14 Initializes servo parameters of Y axis (BFM #15200 to
BFM #15399)
b15 Not available
1 to 1,000,000 times
1 to 1,000,000 times
Appendix A: LIST OF PARAMETERS AND DATA
Appendix A-2 Control Data Table
Default
value
H0000
K1
K1
→ Refer to Section 7.7
11
Reference
12
13
subsection 11.4.15
A
subsection 11.4.16
subsection 11.4.17
167