Changing The Display Unit % To A (Ampere)/V (Volt - Toshiba VF-PS1 Instruction Manual

Variable torque inverter
Hide thumbs Also See for VF-PS1:
Table of Contents

Advertisement

5.15

Changing the display unit % to A (ampere)/V (volt)

 : Current/voltage unit selection
• Function
These parameters are used to change the unit of monitor display.
% ⇔A (ampere)/V (volt)
Current 100% = Inverter's rated current
200V-class voltage 100% = 200Vac
400V-class voltage 100% = 400Vac
Example of setting
During the operation of the VFPS1-2037PL (rated current 16.6A) at the rated load (100% load), units are displayed
as follows:
1) Display in percentage terms


[Parameter setting]
Title
Current/voltage unit selection

* The  converts the following parameter settings:
• A display
Current monitor display
Setting of electronic thermal protection level 1/2
DC braking current
Stall prevention level
• V display
Voltage monitor display
V/f 5-point setting
Note: Base frequency voltage 1, 2 (, ) is always displayed in the unit of V.
Output current:
100%
DC voltage:
100%
Function
: %
: % → A (ampere)/V (volt)
E-25
2)Display in amperes/volts


Adjustment range
, , , 


, , , , 
E6581386
Output current:
16.6A
DC voltage:
200V
(Converted into
AC voltage)
Default setting
5

Hide quick links:

Advertisement

Table of Contents
loading