1.4.4 Installation

Installation environment
The VF-PS1 Inverter is an electronic control instrument. Take full consideration to installing it in the proper operating
environment.
• Do not place any inflammable substances near the VF-PS1 Inverter.
If an accident occurs in which flames are emitted, this could lead to fire.
Prohibited
• Operate under the environmental conditions prescribed in the instruction manual.
Operation under any other conditions may result in malfunction.
Mandatory
• Do not install the VF-PS1 Inverter in any location subject to large amounts of vibration.
This could cause the unit to fall, resulting in bodily injury.
Prohibited
• Check to make sure that the input power supply voltage is +10%, -15% of the rated supply voltage
written on the rating label (±10% when the load is 100% in continuous operation).
If the input power voltage is not +10%, -15% of the rated power voltage (±10% when the load is
100% in continuous operation) this may result in fire.
Mandatory
• Operate in areas where ambient temperature ranges from -10°C to 60°C.
200V class 0.4~45kW, 400V class 0.75~75kW: When installing the inverter where the ambient temperature will rise
200V class 55~90kW, 400V class 90~630kW:
Measuring position
Note: The inverter is a heat-emitting body. Make sure to provide proper space and ventilation when installing in cabinet.
When installing inside a cabinet, we recommend the removal of the protective cover.
Danger
Caution
• Do not install in any location of high temperature, high
humidity, moisture condensation and freezing.
• Avoid locations where there is exposure to water and/or
where there may be large amounts of dust and metallic
fragments.
• Do not install the inverter where there are gases that
corrode metal or solvents that adversely affect plastic.
above 40°C, remove the protective cover from the top cover. When
installing the inverter where the ambient temperature will rise above
50°C, remove the protective cover from the top of it and operate it at
a current lower than the rated one.
When installing the inverter where the ambient temperature will rise
above 45°C, operate it at a current lower than the rated one.
5cm
5cm
Point of measurement of the
ambient temperature
Point of measurement of the
ambient temperature
A-21