[Standard connection diagram - sink logic]
The figure below shows an example of typical wiring in the main circuit 200V 55- 90kW/400V 90-400kW inverter.
*1: Be sure to connect the DC reactor.
*2: To supply a DC power, connect the cables to the PA/+ and PC/- terminals.
*3: If you want to use a DC power supply to operate the inverter, be sure to contact your supplier customer support center,
because an inrush current limiting circuit is required in such a case.
*4: The noise filter is built in for models all of 400V.
*5: For models 200V-90kW and 400V-132kW or larger, three-phase power input is necessary to drive the fan if you want to use
a DC power supply.
*6: Every 200V model of any capacity and every 400V model with a capacity of 220kW or less come with dynamic braking unit
drive circuits (GTR7) built into them as standard equipment, so if your inverter is among these models, connect an external
braking resistor (optional) alone.
*7: If you are using a 400V/250kW model or larger, use a braking unit (optional) and an external braking resistor (optional) in combination.
*8: ⇒ Refer to Section 2.3.2 for switch functions.
*9: The functions assigned to terminals OUT1, VI/II and RR/S4 can be switched by changing parameter settings.
⇒ For details refer to Section 2.3.2.
*10: To supply control power from an external power supply for backing up the control power supplied from the inverter, an
optional control power backup device (CPS002Z) is required. In such a case, the backup device is used at the same time
with the internal power supply of the inverter.
The optional control power backup unit can be used with both 200V and 400V models.
To back up control power, set the parameter  (Control power supply backup option failure monitoring) properly.
⇒ For more information, refer to 6.33.22.
*11: For models 200V-55~90kW and 400V-90~315kW.
*12: For models 400V-400kW.
*13: For PWR connection conforming to safety standards, refer to Section 9.3.