Parameter setting
Positive
Negative
logic
logic
Over-torque detection
Braking resistor
overload pre-alarm
In emergency stop
In retry
PID deviation limit
Run/Stop
Serious failure (OCA,
OCL, EF, phase failure,
etc.)
Light failure (OL, OC1,
2, 3, OP)
Commercial
power/inverter
switching output 1
Commercial
power/inverter
switching output 2
Cooling fan ON / OFF
In jogging operation
(In jog run)
Operation
panel/terminal board
operation switching
Cumulative operation
time alarm
PROFIBUS/DeviceNet/CC
-Link communication error
Forward/reverse
switching
Ready for operation 1
Ready for operation 2
In (pre-)alarm status
Inverter healthy output
RS485
communication error
Error code output 1
Error code output 2
Error code output 3
Error code output 4
Error code output 5
Error code output 6
Specified data output
1
Specified data output
2
Specified data output
3
Function
Operation output specifications (in case of positive logic)
ON:The state that torque component is , set
value or larger continued more than set value.
ON:A certain rate of braking resister overload trip ( )
detection time is over.
OFF:The detection time is within a certain limit.
ON:In emergency stop operation ( is indicated).
OFF:The detection time is within a certain limit.
ON:In retry operation ( is indicated).
OFF:No retry operation is performed.
ON:PID deviation is in or set value.
ON:Running frequency is output or DC injection breaking ( ) is
performed.
ON:Serious failure ( , , , phase failure, abnormal
output, short-circuit) is detected.
OFF:Inverter has recovered from serious failure. (Serious failure
has been reset)
ON:Light failure ( , , , , ) is detected.
OFF:Inverter has recovered from light failure. (Light failure has
been reset)
Refer to Section 6.17.
Refer to Section 6.17.
ON:Cooling fan is in operation.
OFF:Cooling fan is off operation.
ON:In jog run
OFF:In normal operation
ON:In operation by terminal board.
OFF:In operation by operation panel.
ON:Cumulative operation time is beyond the set value.
OFF:Cumulative operation time is less than the set
value.
ON:Communication error occurred.
OFF:Communication error is canceled (reset).
OFF:In forward operation.
ON:In reverse operation.
(The last status is held while operation is suspended.)
ON:In operable status or operation can be started with frequency
command input as an operation switching answer-back.
OFF:In inoperable status.
ON:In operable status or operation can be started with RUN
signal and frequency command input.
OFF:In inoperable status.
ON:More than one of alarm, pre-alarm, undervoltage, low current
over-torque, poor control power supply, PID deviation limit,
abnormal frequency setting or torque limit have occurred or
detected.
OFF:All the alarms above are canceled.
ON and OFF are alternately output at intervals of 1 second.
ON:Communication error occurred.
OFF:Communication error is canceled (reset).
Output the error code in 6-bit.
Output of the designated data in 7-bit.
G-7
E6581386