Toshiba VF-PS1 Instruction Manual page 287

Variable torque inverter
Hide thumbs Also See for VF-PS1:
Table of Contents

Advertisement

(Continued)
4-digit
and 7-
segment
LED
LED
Power Removal safety function
Input/output terminal input
function
Sink/source switching
Failure detection signal
Low speed/speed reach
signal output
[Note 2]
Upper/lower limit
frequency signal output
[Note 2]
Output for frequency
meter/
Output for ammeter
[Note 3]
Pulse train frequency
output
Communication function
Use environments
Ambient temperature
Storage temperature
Relative humidity
Vibration
Note 1: 15 contact input terminals (of which 8 are options) are programmable contact input terminals, and they make it
possible to arbitrarily select from about 80 types of signals.
Note 2: Programmable ON/OFF output terminals make it possible to arbitrarily select from about 180 types of signals.
Note 3: Programmable analog output terminals make it possible to arbitrarily select from about 50 types of signals.
Note 4: 200V class 0.4~45kW, 400V class 0.75~75kW: When using inverters where the ambient temperature will rise
12
200V class 55~90kW, 400V class 90~630kW:
Note 5: Inverters, 18.5kW or greater, do not have wiring port covers. They have large openings, but there is no space
to bend the external cables inside the unit.
Note 6: This function protects inverters from overcurrent due to output circuit ground fault.
Item
Stall prevention during operation, overload limit, overload, undervoltage on power source side, DC circuit
Alarms
undervoltage, setting error, in retry, upper limit, lower limit.
Overcurrent, overvoltage, fin overheat, short circuit on the load side, ground fault on the load side, inverter
overload, arm overcurrent at starting, overcurrent on the load side at starting, EEPROM error, RAM error,
Causes of
ROM error, transmission error, (dynamic braking resistor overcurrent/overload), (emergency stop),
failures
(undervoltage), (low current), (overtorque), (motor overload), (output phase failure)
The items in the parentheses are selectable.
Operation frequency, operation frequency command, forward run/reverse run, output current, DC voltage,
output voltage, compensated frequency, terminal board input/output information, CPU version, control
EEPROM version, past trip history, cumulative operation time, speed feedback, torque, torque command,
Monitoring
torque current, exiting current, PID feedback value, motor overload factor, inverter overload factor, PBR
function
overload factor, PBR load factor, input power, output power, peak output current, peak DC voltage, Motor
counter pseudo PG, position pulse, RR input, VI/II input, RX input, RX2 input, FM output, AM output,
meter adjustment fix output, flash memory version, main circuit EEPROM version, types of connection
option, previous default setting, previous automatic control (AU2)
Display of optional units other than output frequency (motor speed, line speed, etc), current ampere/%
Free unit display
switch, voltage volt/% switch
Automatic edit
Searches automatically parameters that are different from the standard default setting parameters. Easy
function
to find changed parameters.
User default
User parameter settings can be saved as default settings. Allows to reset the parameters to the user-
setting
defined parameter settings.
Charge display
Displays main circuit capacitor charging.
Built-in Power Removal safety function which complies with EN954-1 category 3 and IEC/EN 61508-1
SIL2.
Possible to select positive logic or negative logic with programmable input/output terminal function menu.
[Note 1] [Note 2]
(Default setting: positive logic)
Possible to switch between minus common (CC) and plus common (P24) for control terminal.
(Default setting: minus common (CC))
1c contact output (250Vac-2A-cosФ=1, 250Vac-1A-cosФ=0.4, 30Vdc-1A)
Open collector output (24Vdc, max. 50mA, output impedance: 33Ω)
Open collector output (24Vdc, max. 50mA, output impedance: 33Ω)
Analog output. 1mAdc full-scale DC ammeter or 7.5Vdc-1mA voltmeter
Open collector output (24Vdc, max. 50mA)
RS-485 standard 2-channel equipped (connector: modular 8P)
CC-Link, DeviceNet and PROFIBUS-DP are optional.
Indoor use. Altitude: 3000m or less (current reduction necessary if 1000m or more.) Place not exposed to
direct sunlight and free of corrosive and explosive gases.
-10 to +60°C (Remove the upper cover if 40°C or more, max. 60°C) [Note 4]
-25 to +70°C
20 to 93% (free from condensation)
2
5.9m/s
{0.6G} or less (10 to 55Hz) (Compliant with JIS C60068-2-6)
Specification
above 40°C, remove the covers on top of them, or when
using them where the ambient temperature will rise above
50°C, remove the covers on top of them and lower the output
current.
When using inverters where the ambient temperature will rise
above 45°C, operate each inverter at a current lower than the
rated one.
L-4
E6581386

Hide quick links:

Advertisement