An example of setting when =
Input voltage
Motor speed
• Even after the recovery from an input power failure, the motor continues slowing down to a stop. If the voltage in the
inverter main circuit falls below a certain level, however, control will be stopped and the motor will coast.
• The deceleration time varies according to the setting of . In this case, the deceleration time refers to the time
elapsed before a motor running at (maximum frequency) comes to a full stop.
5.19
Dynamic (regenerative) braking - For abrupt motor stop
: Allowable continuous braking resistance
: Braking resistance overload time
5
• Function
Dynamic braking is used in the following cases:
1) Need to stop the motor quickly.
2) The inverter trips because of an overvoltage (OP) during deceleration.
3) Fluctuation of load condition causes a regenerative power even at a constant speed such as press machine.
[Parameter setting]
Title
* Default settings vary from model dependent. ⇒ Refer to page E-38, 39.
Protection levels defined by (Refer to Section 6.15.2).
Note 1: The time set using is the time for which the resistor sustains an overload. (Enter the time elapsed
before the inverter trips if a load 10 times as large as the allowable continuous braking resistance specified
using is applied.) There is no need to change resistance settings recommended by Toshiba (except
DGP resistance setting).
Note 2: If the parameter is set to or (regenerative braking selected), the inverter will be set automatically so
as to deal with the regenerative energy from the motor by means of a resistor, without taking any action to limit
overcurrent. (The same function as =)
Note 3: For inverters with ratings of 400V-250kW or more, set to , because separate dynamic braking units are
not included as standard equipment.
Deceleration stop
: Dynamic braking selection
: Dynamic braking resistance
Function
Dynamic braking selection
Dynamic braking resistance
Allowable continuous braking
resistance
Braking resistance overload time
Time
Adjustment range
:Disabled
:Enabled (braking resistance overload
detect)
:Select (braking resistance overload
not detect)
~ Ω
~ kW
~ sec.
E-34
E6581386
Default setting
According to model
⇒ Refer to page K-41.
According to model
⇒ Refer to page K-41.