Operating Mode; Operating Mode (X; Read-Out Mode (X - REMEHA Gas 310 ECO Technical Information

Hide thumbs Also See for Gas 310 ECO:
Table of Contents

Advertisement

12

OPERATING MODE

12.1 Operating mode (x [[)

During normal operation the code-display shows the
status (position in cycle) of the boiler, with the t -dis-
play indicating the actual flow temperature.
The digits or letters in the code-display have the follow-
ing meaning:
Code
Description
0
Standby; there is no heat demand from control system
1
Pre-ventilation (pre-ventilation time 30 seconds, post ventilation time 3 seconds)
2
Ignition
3
The burner is firing (flame detection)
4
n/a
5
Waiting mode; check for sufficient air flow using fan and air pressure differential sensor (LDS)
Control stop (burner off + post ventilation) :
- flow temperature T1 > setpoint + 5°
6
- flow temperature T1 > desired setpoint modulating control + 5°
- flow temperature T1 > parameter 1
- difference flow T1 and return T2 > 10° (factory setting); Starting condition is [ 10 °.
End of heating demand, pump run on time. During cycling prevention delay-time the boiler will remain in
7
state 7 and will not react to heat demand.
8
n/a
b
Shut-off mode (see section 12.4)
h
Forced full load (HIGH)
l
Forced part load (LOW)
t
Gas leakage control
c[l Burner cooling
table 11 Operating codes

12.2 Read-out mode (X [[)

Read-out mode is used to display various values. Press
the m key until ! appears in the code window (dot
flashes). Select the required code using the s key.
Code
Description
!
Flow temperature (°)
@
Return temperature (°)
#
Flue gas temperature (°)
%
Heat exchanger temperature (°)
Flow temperature (set point, °)
^
Heat demand status (1
&
sure differential sensor (LDS, 2
Supplied By www.heating spares.co Tel. 0161 620 6677
Read-out range/comments
actual value
actual value
actual value
actual value
Calculated value
0x = on/off-contact open
1x = on/off contact closed
st
digit) and air pres-
x0 = air pressure differential sensor open
nd
digit)
x1 = air pressure differential sensor
closed
37
Read-out
(e.g.)
80
70
85
75
84
11