Installing the inverter
Authorised electrician
7.3
Generator grounding (optional)
Some module manufacturers stipulate that the solar modules must be grounded at the generator (especially when
applied to thin-fi lm modules). An optional grounding kit for use on galvanically isolated Powador inverters is availa-
ble for this purpose.
NOTE
When grounding the generator poles, heed the information provided by the module manufacturer.
Installing the grounding kit
1.
Remove the fuse holder cover with a screwdriver
2. Attach fuse holder using the available screws
3. Connect black cable in the DC terminal with the label "GFDI" (below)
4. Install green/yellow PE cable to the provided PCB attachment using the cable lug
5. For Powador 4202-6002 Plug PE cable with wire sleeve into PE terminal
6. Clamp accompanying cable link into upper GFDI terminal to DC+ or DC-
7.
Activate grounding monitoring in the parameter menu. (See Section 8.3 on page 33)
GN/YE
Figure 17: Powador 2002-3002 with generator grounding kit
BK
BU
RD
Figure 19: Positive grounding on the Powador 2002-3002
Operating Instructions for Powador 2002-6002_EN
GN/YE
BK BU
GN/YE
GN/YE
GN/YE
GN/YE
GN/YE
BK
Figure 18: Powador 4202-5002-6002 with generator
grounding kit (via PE terminal)
GN/YE BU
Figure 20: Positive grounding on the Powador 4202-6002
(via PE terminal)
BK
BU
GN/YE
BK GN/YE
RD