Connecting The Pv Generator To The Device; Designing The Pv Generator - Kaco blueplanet hybrid 10.0 TL3 Manual

Hide thumbs Also See for blueplanet hybrid 10.0 TL3:
Table of Contents

Advertisement

7.4
Connect PV generator to device
7.4.1

Designing the PV generator

Authorised electrician
The maximum generator power (at STC conditions) per input (MPP tracker) must not exceed 6 kW.
CAUTION
Damage to components due to faulty configuration
In the expected temperature range of the PV generator, the values for the no-load-voltage and
the short circuit current must never exceed the values for U
technical data.
Observe limit values in accordance with the technical data.
CAUTION
Grounding the PV system
To ensure proper installation of the PV generator, the PV module frames and mounting
frames in particular must be grounded.
The PV modules themselves (positive or negative pole) must not be earthed!
NOTE
Type and configuration of the PV modules
Connected PV modules must be dimensioned for the DC system voltage in accordance with IEC 61730
Class A, as well as for the value of the AC grid voltage.
It is a transformerless inverter. It can be operated with mono- or polycrystalline PV modules. If you wish
to operate thin-film modules together with the hybrid inverter, please contact the module manufacturer
beforehand to ensure the compatibility of the entire system.
blueplanet hybrid 10.0 TL3
and I
in accordance with the
dcmax
scmax
Page 31