Configuration and Operation
Authorised electrician
Coun-
Menu
try-spec.
level
Settings
AU,DK,
GR-(M/I),
GB-G83, PT,
KR, SI
ES, UD,
IT-CEI021,
GB-G59, IL
DE-NSP,
DE-VDN,
BE, AU,DK,
GR-(M/I), BG,
CZ, FR, PF,
PT, KR, SI
1
2
3
3
All countries
All countries
DE-NSP, BE,
IL, UD
All countries
Operating Instructions for Powador 2002-6002_EN
Display/
setting
Line undervoltage/
overvoltage switch-
off
Minimum/
maximum
grid frequency
Minimum/
maximum
connection voltage
Minimum/
maximum
connection fre-
quency
Connect time
Selection P(f)
Action in this menu/meaning
If the grid frequency exceeds or drops below the con-
fi gured values, the inverter switches off . The minimum
switch-off threshold can be set in 1 V increments.
 Confi gure the switch-off values for undervoltage and
overvoltage.
The inverter continuously monitors the grid frequency. If
the grid frequency exceeds or drops below the confi gured
values, the inverter switches off .
 Set limit values for fast and slow underfrequency
shutdown in 0.1 Hz increments
 Enter the shutdown threshold for fast and slow over-
voltage shutdown.
Shows the minimum/maximum allowable grid frequency.
 Set limit values for underfrequency and overfre-
quency switch-off in 0.1 Hz increments
 Set the shutdown threshold for the minimum and
maximum connection voltage:
NOTE: The limit values cannot be edited for DE-NSP,
DE-VDN and BE.
Shows the minimum/maximum allowable grid frequency.
 Set limit values for minimum and maximum connec-
tion frequency in 0.1 Hz increments.
NOTE: The limit values cannot be edited for DE-NSP,
DE-VDN and BE.
 Set connect time for grid monitoring after fault or
device start in 1 sec. increments.
Off ers the option of regulating the active power depend-
ing on the frequency by two diff erent processes.
 Activate P(f ) mode 1 or mode 2.
NOTE: For DE-NSP and BE, only Mode 2 is permitted.
For IT-CEI021 and DE-MSP is, only Mode 1 is permitted.
P(f ) parameter for the countries/mains types shown in
bold cannot be edited.
 Set f_rise gradient.
 Set f_fall gradient.
NOTE: Set gradients for power limitation with rising and
falling mains frequency in %/Hz. This percentage relates
to the nominal frequency of 50 Hz
 Set f_act.
NOTE: Set the current shutdown frequency.
EN
Page 37