Kaco Powador 2002 Operating Instructions Manual page 22

Hide thumbs Also See for Powador 2002:
Table of Contents

Advertisement

Installing the inverter
Authorised electrician
EN
EN
Figure 16: Connections for DC positive and DC negative
7.2.2.1
Before connecting
Ensure that there is no ground fault
1.
Determine the DC voltage between the
protective earth (PE) and the positive cable of the PV generator, and between the
protective earth (PE) and the negative cable of the PV generator.
If stable voltages can be measured, there is a ground fault in the DC generator or its wiring. The ratio between the
measured voltages gives an indication as to the location of this fault.
2. Rectify any faults before taking further measurements.
3. Determine the electrical resistance between the
protective earth (PE) and the positive cable of the PV generator, and between the
protective earth (PE) and the negative cable of the PV generator.
4. Rectify any faults before connecting the DC generator.
7.2.2.2
Connecting the PV generator
Risk of fatal injury due to electric shock
Severe injury or death will result if the live connections are touched. When there is sunlight present
on the photovoltaic modules, there is DC voltage on the open ends of the DC cables.
Connecting the PV generator
1.
Remove protective caps from the DC connection plugs.
2. Connect PV generator to the DC plug connectors on the underside of the housing.
3. Meet the requirements of protection rating IP65 by closing the unused plug connectors with protective caps.
»
The inverter is connected to the PV generator.
Page 22
DANGER
Do not touch the exposed ends of the cables.
Avoid short circuits.
Operating Instructions for Powador 2002-6002_EN