Kaco Powador 2002 Operating Instructions Manual page 47

Hide thumbs Also See for Powador 2002:
Table of Contents

Advertisement

Maintenance/Troubleshooting
Authorised electrician
Status
Display
FS
42
Line failure:
overvoltage L1
FS
43
Line failure:
undervoltage L2
FS
44
Line failure:
overvoltage L2
FS
45
Line failure:
undervoltage L3
FS
46
Line failure:
overvoltage L3
FS
47
Grid failure:
phase-to-phase
volt.
FS
48
Line failure:
underfrequency
FS
49
Line failure:
overfrequency
FS
50
Line failure:
average voltage
FS
57
Waiting for
reconnect
FS
58
Overtemperature
Control card
FS
59
Self test error
OS 60
Waiting for PV
voltage <550V
OS 61
External
limit (%)
Table 6:
Operating status and fault messages on the display
Operating Instructions for Powador 2002-6002_EN
Explanation
!
The voltage of a grid phase is too high,
the grid cannot be fed into.
The phase experiencing failure is dis-
played.
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
The voltage of a grid phase is too high,
the grid cannot be fed into.
The phase experiencing failure is dis-
played.
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
The voltage of a grid phase is too high,
the grid cannot be fed into.
The phase experiencing failure is dis-
played.
The measured line-to-line voltage is
outside of the tolerance limits.
Grid frequency is too low.
This fault may be grid-related.
Grid frequency is too high.
This fault may be grid-related.
The grid voltage measurement accord-
ing to EN 50160 has exceeded the
maximum permitted limit value.
This fault may be grid-related.
Waiting time of the inverter after a
fault.
The temperature inside the unit was
too high. The inverter switches off to
prevent damage to the hardware.
A fault occurred during a self-test.
The inverter does not begin feeding
into the grid until the PV voltage falls
below a specifi ed value.
The external „Power Control" limit was
activated by the grid operator. The
inverter limits its power.
Action
By
 Notify your
E
authorised elec-
trician.
 Notify your
E
authorised elec-
trician.
 Notify your
E
authorised elec-
trician.
 Notify your
E
authorised elec-
trician.
 Notify your
E
authorised elec-
trician.
 Notify your
E
authorised elec-
trician.
 Notify your
E
authorised elec-
trician.
 Notify your
E
authorised elec-
trician.
Inverter does not
switch on again until
a country-specifi c
time has elapsed.
 Provide for suffi -
E
cient ventilation.
 Notify your
E
authorised elec-
trician.
-
-
-
-
Page 47
EN