Maintenance/Troubleshooting
Authorised electrician
Status
Display
FS
10
Temperature in
EN
EN
unit too high
FS
18
Resid. current
shutdown
FS
29
Ground fault
Check fuse
FS
30
Fault
Transformer fault
FS
31
RCD module
error
FS
32
Fault
Self-test
FS
33
Fault
DC feed-in
FS
34
Communication
error
FS
35
Protection shut-
down SW
FS
36
Protection shut-
down HW
FS
38
Error
PV overvoltage
FS
41
Line failure:
undervoltage L1
Table 6:
Operating status and fault messages on the display
Page 46
Explanation
!
In case of overheating, the inverter
switches off . Possible causes:
ambient temperature too high,
fan covered,
inverter defective.
Residual current was detected. The
feed-in was interrupted.
A ground fault was detected at the PV
generator.
The current and voltage measure-
ments in the inverter are not within
acceptable range.
An fault has occurred in the AC/
DC-sensitive residual current device.
The internal grid separation relay test
has failed.
The DC feed-in has exceeded the per-
mitted value. This DC feed-in can be
caused by grid conditions and may not
necessarily indicate a fault.
A communication error has occurred
in the internal data transmission.
Protective shutdown of the software
(AC overvoltage, AC overcurrent, DC
link overvoltage, DC overvoltage).
Protective shutdown of the
hardware (AC overvoltage, AC overcur-
rent, DC link overvoltage).
The voltage of the DC generator is too
high. The PV generator is confi gured
incorrectly.
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
Action
 Clean the fans.
 Notify your
authorised elec-
trician.
 Notify your
authorised elec-
trician.
 Notify your
authorised elec-
trician.
-
 Notify your
authorised elec-
trician if the fault
occurs several
times.
 Notify your
authorised elec-
trician if the fault
occurs multiple
times.
 Notify your
authorised elec-
trician.
 Check the data
cable.
Not a fault
Grid-related
shutdown,
the grid connects
again automatically.
Not a fault
Grid-related
shutdown,
the grid connects
again automatically.
 Notify your
authorised elec-
trician.
 Notify your
authorised elec-
trician.
Operating Instructions for Powador 2002-6002_EN