Installing the inverter
Authorised electrician
Model
Powador 2002
EN
EN
Powador 3002
Powador 4202
Powador 5002
Powador 6002
Table 4:
Recommended conductor cross-sections and fuse protection of NYM cables
NOTE
When the line resistance is high (i.e. long grid-side cables), the voltage at the grid terminals of the
inverter will increase during feed-in to the grid. The inverter monitors this voltage. If it exceeds the
country-specifi c grid overvoltage limit value, the inverter switches off .
Figure 13: Insert AC leads into the connection area
Making the grid connection
↻ Use cables with three wires (L1, N, PE).
1.
Loosen cable fi tting for AC connection.
2. Remove the outer cladding of the AC cables.
3. Insert the AC leads through the cable fi tting into the connection area. (See Figure 13 on page 20)
4. Strip the insulation from the AC cables.
5. Guide the AC leads through the ferrite cores.
6. Wrap the AC leads once around the ferrite cores. (See Figure 14 on page 20)
Page 20
Conductor cross-sec-
tion
1.5 mm²
2.5 mm²
4.0 mm²
4.0 mm²
6.0 mm²
Ensure that the conductor cross-sections are suffi ciently large or that the cable lengths are suffi -
ciently short.
Fuse protection: gL safety fuses
16 A for 1.5 mm² conductor cross-section
20 A for 2.5 mm² conductor cross-section
25 A for 4.0 mm² conductor cross-section
25 A for 4.0 mm² conductor cross-section
35 A for 6.0 mm² conductor cross-section
Figure 14: AC leads wound around the ferrite cores
Operating Instructions for Powador 2002-6002_EN