Configuration and Operation
Authorised electrician
Coun-
Menu
try-spec.
level
Settings
DE-NSP , BE
1
2
3
3
IT-CEI021
IT-CEI021,
1
2
3
3
UD, IL
1
2
3
3
DE-NSP, BE,
IT-CEI021, IL,
UD
1
2
3
3
1
2
3
3
IT-CEI021
1
2
3
3
DE-NSP, BE
Operating Instructions for Powador 2002-6002_EN
Display/
setting
Reactive power
setting
Additional
processes
Q specifi cation
active
cos phi specifi cation
active
cos phi (P/Pn) active
cos phi (P/Pn)
parameter?
Q(U) characteristic
Action in this menu/meaning
The following control methods can be set. At least one
mode must be active.
- cos phi (P) : specifi c characteristic
- cos phi (P) : standard characteristic
- cos phi : x.xxx u (under excited) / o (over excited) (const)
- Q: xx.x % u (under excited) / o (over excited) (const)
- Q=f(U) standard characteristic
Q=f(U) specifi c characteristic with 5 nodes
Q=f(U) specifi c characteristic with two-state controller
Set the idle power Q (in % of device nominal power)
to a fi xed value.
Select the type of phase shift (under-excited (u) /
over-excited (o)).
Confi gure power factor.
If a power factor not equal to 1 is selected: Select the
type of phase shift (under-excited (u) /over-excited
(o)).
The selection enables display, resetting or editing the
nodes. (min. 2 / max. 10)
Displays: All nodes are displayed in succession.
Reset: Press "1" to activate default characteristic and a
confi rmation message is shown.
Edit: Specify the number of nodes for editing.
–
Increment P/Pn in % with key "2" and confi rm with
key "1".
–
Increment cos phi with key "2" and confi rm with key
"1".
NOTE: If a power factor not equal to 1 is selected: Select
the type of phase shift (under-excited/over-excited).
NOTE: After running through all selected nodes, all values
are saved by pressing "1" and this characteristic then is
checked for consistency.
NOTE: In the event of an error, the characteristic that was
previously active is restored and the error message "Char-
acteristic invalid" appears.
You then have the option of correcting the characteristic.
Additional parameters can be set when cos phi (P/Pn)
function is active.
Specify gradient k. (Default value: 01000/1000)
Specify change time. (ms)
U_Lock In and U_Lock Out power range set as ‰ of
rated power, in which the network support process is
active.
Specify the target voltage.
Specify gradient.
Specify change time.