Maintenance/Troubleshooting
Authorised electrician
Status
Display
OS 62
Standalone mode
EN
EN
PAC ####W
(###%)
OS 63
Measured values
OS 64
Measured values
FS
66
Voltage trans.
fault
FS
70
Fan error
FS
Confi g. error
Invalid CRC
Table 6:
Operating status and fault messages on the display
Page 48
Explanation
!
The inverter was switched to islanding
operation by the Powador Grid-Save.
The inverter is disconnected from the
public low-voltage grid. The power
indicator percentage refers to the max-
imum AC power.
P(f )/frequency-dependent power
reduction: Frequency-dependent
power reduction will be activated
when the BDEW (German Associa-
tion of Energy and Water Industries)
Medium Voltage Directive goes into
eff ect. Power reduction starts at a fre-
quency of 50.2 Hz.
Output current limiting: The AC cur-
rent is limited once the specifi ed maxi-
mum value has been reached.
Plausibility test of ADC test between
ARM and DSP has failed
The fan is malfunctioning.
The checksum of the loaded confi g.
fi le does not match the checksum
in the EEPROM. This means that the
EEPROM data originate from a diff er-
ent confi g. fi le.
Action
-
-
-
 In case of
repeated occur-
rence:
Notify your
authorised elec-
trician.
 Replace
defective fan
 Notify author-
ised electrician /
KACO Service
Operating Instructions for Powador 2002-6002_EN