Configuration and Operation
Authorised electrician
Coun-
try-spec.
Settings
EN
EN
All countries
All countries
ES, ,GB-G59,
IT-CEI021,
UD,IL
DE-NSP, BE
ES , GB-G59,
IT-CEI021,
UD, IL
BG, CZ,
FR,PF, DE-
VDN
BG, CZ, FR ,
PF, DE-VDN
AT
Page 36
Menu
Display/
level
setting
1
2
3
3
"Parameters" menu
Select country
1
2
3
3
Set grid
parameters
Overvoltage
shutdown
1
2
3
3
Undervoltage
shutdown
Max. line voltage
EN 50160
Voltage drop
between meter and
inverter
Undervoltage
shutdown
Overvoltage
shutdown
Action in this menu/meaning
Only service technicians are permitted to make changes
in the parameter menu.
↻ You are in menu level "1".
↻ The unit name is displayed.
 Press "2" for at least 15 seconds to run through menu
level 3.
The default setting is used if "no" is selected.
1.
Set the desired country setting.
NOTE: This option infl uences the country-specifi c oper-
ating settings of the inverter. Please consult KACO service
for further information.
 Provides the option to set the grid parameters.
1.
Confi rm "Yes" input using "1" key.
2. Set the required grid parameters in the next menu.
 If "No" is selected, the defi ned country-specifi c param-
eters will be used.
 Specify the shutdown threshold
for fast and slow overvoltage shutdown.
 Set period from occurrence of the fault to shutdown
of the inverter.
 Activate or deactivate password protection.
 Specify the shutdown threshold
for overvoltage shutdown.
The 10-minute average for the measured voltage as
per EN50160 is used.
 Set period from occurrence of the fault to shutdown
of the inverter.
 Specify the shutdown threshold
for fast and slow undervoltage shutdown.
 Set period from occurrence of the fault to shutdown
of the inverter.
The grid voltage is averaged over ten minutes. If the
defi ned value is exceeded, the inverter is disconnected
from the grid.
 Enter the four-digit password using key "2". The pass-
word is unit-specifi c.
 Set voltage threshold.
The voltage drop between the inverter and the grid-feed
meter is added to the limit value that was set for grid
shutdown according to EN 50160. The limit value can be
set from 0 to 11 V in 1 V increments.
 Specify the switch-off value for the voltage drop (0 to
11 V).
Displays the limit values for undervoltage or overvoltage
shutdown.
 Defi ne limit values for undervoltage or overvoltage
shutdown.
Operating Instructions for Powador 2002-6002_EN