Removing Drain-Up Mechanism; Removing Float Switch - Hitachi RPI-0.8FSG1 Service Manual

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

2.4.9 Removing Drain-Up Mechanism

(1) Remove the drain pan according to the item 2.4.8 "Removing Drain Pan".
(2) Remove the hose band and remove the drain hose.
(3) Remove screw of earth wiring.
(4) Hold the drain-up mechanism and remove three (3) screws of the fixing plate for the drain-up
mechanism.
(5) Remove the drain-up mechanism with the
fixing plate.

2.4.10 Removing Float Switch

(1) Remove the drain pan according to the item 2.4.8 "Removing Drain Pan".
(2) Loosen the resin nut for fixing the float switch and remove the float switch.
Remove two (2) screws of fixing base for fixing the drain-up mechanism when removing the drain-up
mechanism.
NOTE:
Carefully handle the float switch.
Do not drop it on the floor. If dropped, malfunction may occur.
When mounting, attach the float switch to the fixing plate by hand.
(Do not use a motor-driven screwdriver.)
TURN OFF all power source switches.
Screw for Earth Wiring
Screws
Drain-Up
Mechanism
Screw for
Fixing Plate
Nut
Float Switch
Tool
Phillips Screwdriver
Fixing Plate
Drain Hose
Hose Band
Tool
Phillips Screwdriver
Screw for
Fixing Plate
Fixing Base
Drain-Up Mechanism
SERVICING
(2.4 4-Way Cassette Type)
2-61

Hide quick links:

Advertisement

Table of Contents
loading