Installation Inspection; Alarms; Resetting The Interface - Uponor Climate Control Zoning System Installation Manual

Radiant heating and cooling systems
Table of Contents

Advertisement

Setting the Heat Demand Management
1. Uponor screen
Parameters
2. Choose Common or Individual.
>
Press OK.
STOP
Setting the Exercise Setup
Schedule a weekly five-minute activation to maintain the
functionality of the valves and pumps.
1. Uponor screen
Parameters
Exercise Setup
Cancel Exercise
Exercise Valve and Pump
Exercise Valve Only
Exercise Time
Monday
1 : 00

Installation Inspection

Completely check the installation.
1. Review Base Unit Installation Section.
• Confirm that the interface and thermostats
are powered.
• Check the interface for alarms.
2. Close the base unit cover.
3. Complete the installation report in Section 12.
4. Give this manual and all information about the system
to the user.
24
>
>
Main Menu
Settings
>
Heat Demand Management
Heat Demand Manage
Please choose heat demand
Common
A common pump relay must
not be connected to more than one base unit.
>
>
Main Menu
Settings
>
Valve/Pump Exercise
2. Select the preferred parameter.
>
Press OK.
3. Set the day and time for
the exercise.
>
Press OK.

Alarms

>
System
To diagnose and resolve alarms, see
Section 11: Troubleshooting.
1. Uponor screen
management type.
>
All Alarms
Individual
Room List
! [14/06] Base Unit 3
! [14/06] System
Clear Alarm List
Clear Alarm List
Erase all alarms?
Yes
>
System
Make sure you have resolved all the alarms
before clearing the list.

Resetting the Interface

Should an error occur and the interface is not functioning
normally, restart the system.
Briefly press the reset button. New installation and
registration is not necessary, but the time and date must
be reset.
>
>
Main Menu
Information
>
2.
Clear alarm list.
>
3.
Press OK.
No