Installing thermostats ......... 9.13 CAL – Calibration ..........Selecting locations for thermostats....9.14 OFF – Standby mode ........Installing Uponor Thermostats T-36 and T-38. 9.15 Lock mode ............5.2.1 Opening the thermostats ......... UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
Page 3
10.11 Menu tree ............Maintenance ..........11.1 Manual preventive maintenance ...... 11.2 Automatic preventive maintenance....11.3 Corrective maintenance........11.3.1 Fallback mode..........11.3.2 Resetting the controller ........11.4 Troubleshooting..........Technical data ..........UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
While Uponor has made efforts to ensure that the Manual is accurate, Uponor does not guarantee or warrant the accuracy of the information contained herein. Uponor reserves the right to...
We cannot accept any responsibility for damage or breakdown that can result from ignoring these instructions! Power WARNING! The Uponor system uses 50 Hz, 230 V AC power. In case of emergency, immediately disconnect the power. Technical constraints CAUTION To avoid interference, keep installation/data cables away from power cables of more than 50 V.
Designed for maximum comfort, the thermostats T-37 and T-38 communicate with the controller by non-polarized two wired cables. It is possible to mix the different types of Uponor wired For example, the maximum limitation can protect a thermostats in the same installation.
Uponor Controller, 6 Channels C-33 Wired Pos. Uponor designation Description The Uponor Controller, 6 Channels C-33 Wired controls up to 6 Uponor Controller, 6 6-channel controller thermostats and 8 actuators connected to the hydraulic system of Channels C-33 Wired the installation.
Can be set to permanent override mode • Hidden reset 3.3.3 Timer • Powered by controller (no batteries) Uponor Timer I-36 can be connected to control the system. Display shows: Uponor Timer I-36 wired • Setpoint temperature Main characteristics: •...
3.3.4 Uponor Actuators Uponor actuators are mounted on top of the valves of the manifolds When the thermostat senses that the temperature has fallen below the setpoint, the controller sends a signal to the actuator to open the valve. The indicator window on the actuator turns bright.
Installing the Uponor Control System Wired Installation procedure 2. Check that the connectors and switches are easily accessible. Uponor recommends that you follow the steps described below CAUTION to achieve the best possible installation: The Uponor Controllers C-33 and C-35 must be Section Description mounted horizontally.
01. All actuators on rows 01 to 04 are controlled from the same thermostat. The next thermostat, #05, controls the actuators on rows 05 to 11 and thermostat #12 controls the actuator on row 12. UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
Heating Cooling Controller C-33 Timer control zone 2 No cooling for this room Uponor Controller C-33 can only be used for heating. One to six thermostats and one to eight actuators can be connected to this NOTE! controller. The two wires from the thermostat are non-polarized.
(B)on the upper part of the lid. 4.3.6 Connecting a heating–cooling switch If the installation is equipped with a cooling unit, the Uponor Control System Wired can be run through a heating–cooling switch. The controller heating–cooling input operates with the...
4.4.5 Uponor Controller C-35 with four thermostats, timer and heating–cooling switch, page 15 4.4.1 Uponor Controller C-33 A connection example of Uponor Controller C-33 is shown in the figure below. • Thermostat #01 controls the actuators on channels 01a and •...
4.4.4 Uponor Controller C-35 with four thermostats and timer A connection example of Uponor Controller C-35 using four thermostats is shown in the figure below. NOTE! When connecting thermostats and actuators to the Uponor Controller, the auto-linking rules must always be followed strictly.
Page 16
If a Uponor Timer I-36 is connected to the Uponor Controller C- 35 and the system is operating in cooling mode, then zone 1 and Timer zone 2 will automatically be combined to a single zone.
2. Ensure that the 230 V AC compartment of the controller is closed and the fixing screw is tightened. 3. Connect the power cable to a 230 V AC wall socket. UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
2. Ensure that the thermostat is away from direct solar 5.2.2 Mounting the thermostats radiation. Uponor Thermostats T-36 and T-38 are delivered in kits including 3. Ensure that the thermostat will not be heated through the screws and plugs. wall from sunshine.
It is possible to connect a floor sensor or a remote indoor sensor to Uponor Thermostats T-36 and T-38. 5.3.2 Mounting the thermostats Uponor Thermostat T-34 is delivered in a kit including screws and 1. Insert the two wires of the sensor cable into the connector plugs. terminals labelled 3 and 4.
5.4.2 Mounting thermostats onto a wall The Uponor thermostats are delivered in kits including screws and wall plugs. The Uponor thermostats can be mounted either directly onto a wall or using a 60 mm European wall box. See figure below.
1. Use a cross-headed screwdriver to set the potentiometer. See figure below. 5.4.4 Connecting optional floor sensor Uponor Thermostats T-33 and T-37 allow a floor sensor to be fitted to the system. The temperatures thus measured ensure a more efficient management of the system. Wiring the floor sensor 1.
4.3 Connecting components to controller, page Connecting an optional dry contact It is possible to connect a dry contact input to Uponor Timer I-36, for example a Uponor Remote Access Module R-56. 1. Insert the two wires of the dry contact cable into the connector terminals labelled 3 and 4.
3. Close the covers of the controller and the thermostats. Fill in the “Installation report” on the centre pages of booklet. 5. Give the manual and all information about the system to the user. UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
Operating Uponor Control System Wired The Uponor Control System Wired controls the floor heating/ cooling installation according to customer needs. Temperatures are adjusted with thermostats located in each room. Principle of operation As soon as the temperature measured at a thermostat is lower...
Page 25
1. Carefully remove the dial using a small, flat-bladed screwdriver. 2. Set the minimum temperature limit with the blue stopper (A). 3. Set the maximum temperature limit with the red stopper (B). UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
0 or 5 Used with suitcase icon, see pos. B above. Temperature unit, shown when the character group A shows a temperature UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
ECO or comfort, as defined by the • Heating or cooling icon depending on system working mode programming. • ECO or comfort mode icon depending on system working mode UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
9. Press the + and - buttons to change the setting. There are three alternatives: 10. Press OK to confirm the setting. • Monday till Friday, default setting • Monday till Saturday UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
9.10 BAL – Balancing mode. • Set the clock to the time for the first comfort/economy If RFT regulation mode is selected, the next regulation changeover. setting, is displayed. UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
Default setting: 4 °C Entering standby mode Setting range: 0 – 11 °C 1. Press OK to confirm the standby mode. Setting accuracy: 0.5 °C The standby icon and the room temperature is displayed. UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
Other displayed information remains and the thermostat operates as set-up. Exiting lock mode 1. Press and hold the + and - buttons simultaneuously for three seconds. The lock icon disappears. UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
9.16 Menu trees The following sections show the menu trees for Uponor Thermostats T-36 and T-38 9.16.1 Uponor Thermostat T-36 Run mode, see section 9.4, page 27 Regulation choices, see section, see section 9.9, page 29 Room sensor regulation, see section 9.9, page 29...
Operating Uponor Timer I-36 Uponor Timer I-36 has a screen with a number of icons and Pos. Icon Description symbols for displaying messages. Manual override. For example forced Below the screen there are three buttons for operating Uponor comfort or economy mode.
Remote system controlled forced economy mode Forced economy mode ina zone can be set from a remote external system such as the Uponor R-56 SMS module. Then the empty 10.4 Run mode house and hand icon are flashing. In this case it is not possible to cancel the forced mode from the timer.
10. Press and hold the OK key for 3 seconds to select the default 2. If required, press the + or - button to change zone. schedule. 3. Press OK to start the programming. UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
1 d flashing, designating the number of days the holiday The lock icon disappears. mode is active 2. Press the + and - buttons to set the number of days the holiday mode shall be active. UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
10.11 Menu tree The structure below illustrates the menu tree of Uponor Timer I-36. Run mode, see section 10.4, page 34 Clock settings, see section, see section 10.6, page 34 Year, see section, see section 10.6, page 34 Month, see section, see section 10.6, page 34...
Do not use any detergents to clean the Uponor System components. 11.2 Automatic preventive maintenance Uponor Control System Wired is fitted with an automatic exercise function. This function consists of a test run designed to prevent the pump and actuators from seizing up due to inactivity.
Page 39
2. Check that the actuators are connected to the same zone in the controller as on the manifold. 3. Check that thermostatsare connected to the correct zone in the controller. UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
Page 40
1. To return to nomal scheduling will not follow the into econony mode by a remote mode the dry contact input specified time scheduling system must be opened again by the remote system. UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
C-33/C-35 to heating/cooling relay — 20 m 0.2 – 1.5 mm C-33/C-35 to timer — 0.2 – 1.5 mm C-33/C-35 to dew-point sensor module — 20 m 0.2 – 1.5 mm UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
Page 42
Connectors for dew-point sensor unit • Red = Heating mode Connectors for 1–14 actuators • Green = Heating–cooling mode Connectors for 1–12 thermostats • Off = Power off 230 V AC compartment C-35 wiring diagram UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
Page 43
Pos. Description Connectors for 1–8 actuators Power indicator Connectors for 1–6 thermostats • Red = Power on (heating mode) 230 V AC compartment • Off = Power off C-33 wiring diagram UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
Page 44
Installation report Controller No. Channels Rooms Floor sensor Relay +24 V DC 230 V AC Pump Timer UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
Page 45
UPONOR CONTROL SYSTEM WIRED - INSTALLATION AND OPERATION MANUAL...
Page 46
Uponor Housing Solutions Ltd. Snapethorpe House Rugby Road, Tel. +44 1455 550 355 Lutterworth Leicestershire LE17 4HN Fax +44 1455 550 366 www.uponorhousingsolutions.co.uk Uponor reserves the right to change specifications without prior notice, in keeping with our policy of continuous improvement and development.
Need help?
Do you have a question about the UponorControl System and is the answer not in the manual?
Questions and answers