Set Gas Input Rate - Carrier 58MXA Installation, Start-Up, And Operating Instructions Manual

Deluxe 4-way multipoise fixed-capacity direct vent condensing gas furnace sizes 040o140, series 170
Table of Contents

Advertisement

NOTE: I f TEST/TWIN
andCOM-24V
terminals are jm_apered
longer than
2 sec, LED
will flash
rapidly
and ignore
component
test request
Component
test sequence
is as ibllows:
a. LED will display
previous
stares
code 4 times.
b. Inducer
motor
starts
and continues
to run until
Step g of
component
test sequence.
c. After 7 seconds
the hot surface
igniter
is energized
for 15
see., then of£
d. Blower
motor
operates
on (ontinuous=FAN
speed
for 10
see.
e. Blower
motor
operates
on HEAT
speed £_r 10 sec.
£ Blower
motor
operates
on COOL
speed _br 10 sec.
g. Inducer
motor
stops.
5. Reconnect
R lead to furnace
contlol,
remove
tape fiom blower
door switch,
and re=install
blower
door.
6. Operate
furnace
per instruction
on outer door.
7. Verii}"
ihmace
shut
down
by lowering
thermostat
setting
below
room temperature.
8. Verify7 that filrnace
restarts
by raising
them_ostat
setting above
roonl
temperature
Step
5--Adjustments
SET GAS INPUT
RATE
Furnace
gas input rate on rating plate is %r installations
at altitudes
up to 2000 ft.
In the U.S.A.,
the input ratings
for altitudes
above 2000 ft must be
reduced
by 2 percent
fbr each
1000 ft above
sea level.
In Canada,
the input
ratings
must
be derated
by 5 percent
for
altitudes
between
2001 ft to 4500 ft above sea level.
Furnace
input rate must be within ÷ 2 percent
of input
on [_urnace
rating
plate
adjusted
for altitude
1. Determine
natural
gas orifice
size and manifPld
pressure
for
correct
input
a. Obtain
average
gas heat value
(at installed
altitude)
fi'om
local
gas supplier.
b. Obtain average
gas specific
gravity
fiom local gas supplier
c. Verii}' f_m'nace model
and size. Table 9 can only be used for
model
5gMXA
fhmaces
with
rating
plate
heating
inputs
(1000's
Btuh)
of 040 through
120. Table
10 can only be
used fbr model
58MXA
fhmaces
with a heating
size of 140.
d. Find installation
altitude
in Table 9 or 10.
NOTE:
For Canadian altitudes of 2001 to 4500 It, use L.SA
altitudes of 200! to 3000 ft in Table 9 or 10.
e. Find closest natural gas heat value and specific gravity in
Table 9 or 10.
£ Follow
heat value
and specific
gravity
lines
to point
of
intersection
to find
orifice
size
and
manifbld
pressure
settings
fbr proper
operation.
--€
42
EXAMPLE:
(0-2000
fi altitude
using Table
9)
Heating
value
1050 Btuicu
ft
Specific
gravity
0.62
TherefPre:
Orifice
No
45 and
Manifold
pressure
3 6-in.
wc
* Furnace
is shipped
with No. 45 orifices
In this
example
all main burner
orifices
are the cmTect size
and do not need to be changed
to obtain
the proper
input rate.
Check and verify7 burner
orifice
size in fEmace.
NEVER
ASSL ME
ORIFI(E
SIZE; ALWAYS
CHECK
AND VERIFY
2. Adjust
mani_bld
pressure
to obtain
input
rate
NOTE:
Manifold
pressure
must
always
be measured
with burner
enclosure
fiont
REMOVED
Gas meter
must
always
be clocked
with burner
enclosure
flout INSTALLED.
a Remove
burner
enclosure
fi'ont
b. Remove
seal cap that
conceals
adjustment
screw
for gas
valve regulator.
(See Fig. 57.)
c Jumper
R and W thermostat
connections
on control
to start
_/rnace,
d. Turn
adjusting
screw,
cmmterclockwise
(out) to decrease
manifold
pressure
or clockwise
(in) to increase
manifbld
pressure
NOTE:
This furnace
has been approved
for a manifold
pressure
of 3.2 in. wc to 3.S in. wc when installed
at altitudes
up to 2000 ft.
For altitudes
above 2000 It, the manifold
pressure
can be adjusted
from
2.0 in. wc to 3.S in. we. If manifold
pressure
is outside
this
range,
change
burner
orifices
to obtain
pressure
in this range.
UNIT DAMAGE
HAZARD
Failm'e to fbllow this caution may result in reduced furnace
1ilk
DO NOT bottom-out
gas valve regulator adjusting
screw
This can result in unregulated manifold pressure and result in
excess overfire and heat exchanger failures.
NOTE:
If orifice hole appears
damaged
or it is suspected
to have
been
redrilled,
check
orifice
hole
with
a mm_bered
&ill
bit of
con'ect
size.
Never
re&i!l
art orifice
A bun'-flee
and squarely
aligned
orifice
hole is essential
for proper
flame
characteristics.
._
.
®
u
UNIT
DAMAGE
HAZARD
Failure
to
%tlow
this
caution
may
result
in
component
damage
due
to
flame
impingement
of burners
and
heat
exchangers.
DO NOT
re&ill
orifices.
Improper
&illing
(burrs,
out-o_=
round
holes,
etc.)
can
cause
excessive
burner
noise
and
misdirection
of burner
flames.
(See Fig. 58.)
e. Replace gas valve regulator adjustment screw seal cap.
£ Replace burner enclosure fiont and verify adjusted gas
input rate using method outlined in item 3
g. Look through sight glass in bmner enclosure and check
burner flame Burner flame should be clear blue, almost
tlanspareat. (See Fig 590
h. Remove jumper fiom R and W
Verify natural gas input rate by clocking gas meter.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents