Carrier 58MXA Installation, Start-Up, And Operating Instructions Manual page 9

Deluxe 4-way multipoise fixed-capacity direct vent condensing gas furnace sizes 040o140, series 170
Table of Contents

Advertisement

COLLECTOR
BOX -'_
DRAIN TUBE (BLUE)
TUBE
(GREEN)
EXTENSION
TUBE
COLLECTOR
BOX
TUBE
(PINK)
DRAIN
TUBE
(BLUE
& WHITE
STRIPED)
COLLECTOR
BOX
EXTENSION
TUBE
TRAP
©
iNDUCER
HOUSING
DRAIN
TUBE
(VIOLET)
/
A94165
Fig.
8--Downflow
Tube
Configuration
(Left-Hand
Trap Instatlat{on)
(2)
Condensate
Trap Located
on Right
Side of (asing
(a)
Install
drain
tube
coupling
d5ctow-supplied
in
loose
parts
bag)
into
collector
box
drain
robe
(blue
and white
striped
label) which
was previo
ously plugged.
(b)
Connect
larger
diameter
&ain
robe
(gmtoryo
supplied
in loose
parts
bag)
to &ain
tube couo
piing,
extending
collector
box
drain
robe
for
connection
to condensate
trap
(c.)
Route
extended
collector
box &ain tube directly
from
collector
box
&ain
to condensate
trap
as
shown
in Fig. 9.
(d)
Determine
appropriate
length
and cut
(e)
(onnect
to condensate
trap
(f.) Clamp
robe to prevent
any condensate
leakage.
2. Inducer
Housing
Drain
Tube
a. Remove
fi_ctoL-y-installed
cap and
clamp
from
LOWER
inducer
housing
drain connection.
b. Remove
and
discard
UPPER
(molded)
inducer
housing
&ain robe which
was previously
connected
to condensate
t_ap,
c Install
cap and clamp
on UPPER
inducer
housing
&ain
connection
where
molded
&ain robe was removed.
d. Use inducer
housing
&ain
robe (violet
label and factory°
supplied
in loose
parts
bag) to connect
LOWER
inducer
housing
&ain connection
to the condensate
trap.
e. Connect
inducer
housing
drain
connection
to condensate
trap.
(1.) Condensate
Trap Located
on Left Side of Casing
(a.)
Detemline
appropriate
length
and cut.
O
O
©
,DRAIN TUBE _1_
COUPLING
Fig.
_PLUG
_CAP
_---COLLECTOR
BOX
DRAIN
TUBE(BLUE)
_
COLLECTOR
BOX
TUBE
(PINK)
COLLECTOR
BOX
TUBE
(GREEN)
COLLECTOR
BOX
EXTENSION
TUBE
COLLECTOR
BOX
DRAIN
TUBE
(BLUE
& WHITE
STRIPED)
_-
COLLECTOR
BOX
EXTENSION
TUBE
INDUCER
HOUSING
;
RAIN
TUBE
(VIOLET)
CONDENSATE
TRAP
b F'_'- COLLECTOR
BOX
EXTENSION
DRAIN
TUBE
A94166
g--Downflow
Tube Configuration
(Right-Hand
Trap Installation)
(b.) Connect
tube to condensate
trap,
(c,) Clamp
robe to prevent
any condensate
leakage
(20
(ondensate
Trap Located
on Right
Side of Casing
(a.) Route
inducer
housing
drain
tube (violet
label)
directly
from inducer
housing
to condensate
trap
as shown
in Fig. 9.
(b)
Determine
appropriate
length
and cut
(c.) Connect
robe to condensate
trap.
(d)
(lamp
robe to prevent
any condensate
leakage.
3. Relief
Port Tube
Re_r
to Pressure
Switch Tubing
section _br connection
procedure.
CONDENSATE
TRAP
FIELD
DRAIN
ATTA(HMENT
Refkr
to
Condensate
Drain
section
for recommendations
and
procedures.
PRESSURE
SWITCH
TUBING
One collector
box pressure
tube (pink label) is factory connected
to
the pressure
switch
_br use when furnace
is installed
in UPFLOW
applications.
This
robe MUST
be disconnected
and used
for the
condensate
trap relief port robe. The other
collector
box pressure
robe (green
label) which
was i:i_ctory connected
to the condensate
trap relief
port connection
MUST
be connected
to the pressure
switch
in DOVvL\TLOW
or HORIZONTAL
RIGHT
applications.
NOTE:
See Fig. 8 or 9 or robe routing
label on main fi/mace
door
to check
for proper
connections.
1. Disconnect
collector
box pressure
robe (pink label) attached
to
pressure
switch.
2. Extend
collector
box
pressure
robe (green
label)
which
was
previously
connected
to condensate
trap relief port connection
by splicing
to small diameter
robe d;actou-supptied
in loose
parts bag).