Carrier 58MXA Installation, Start-Up, And Operating Instructions Manual page 25

Deluxe 4-way multipoise fixed-capacity direct vent condensing gas furnace sizes 040o140, series 170
Table of Contents

Advertisement

(
NOT IN
HORIZONTAL
SECTION
FURNACE
TRANSITION
IN
VERTICAL
SECTION
A93034
Fig. 32--CombustionoAir
and Vent Pipe Diameter
Transition
Location
and Elbow Configuration
FIRE
AND
EXPLOSION
HAZARD
Failure
to follow
this warning
could
result
in fire, property
damage,
personal
injury,
or death.
Solvent
cements
are
combustible.
Keep
away
h'om
heat,
sparks,
and open
flame.
Use only
in well-ventilated
areas.
Avoid
breathing
in vapor
or allowing
contact
with
skin or
eyes.
CARBON
MONOXIDE/PROPERTY
DAMAGE
Failure
to
follow
this
warning
could
result
in
property
damage,
personal
injury,
or death.
All
combustion-air
and
vent
pipes
must
be
airtight
and
watertight
Pipes must also tem_inate
exactly
as shown in Fig.
36, 37, 38, 39, or 40.
PROPERTY
DAMAGE
Failure
to %llow
this caution
may result in dripping
condeno
sate and potential
property
damage.
When
combustion-air
pipe
is installed
above
a suspended
ceiling,
pipe must
be insulated
with
3/8oin.
thick Armaflexo
type insulation.
( ombustionoair
pipe should also be insulated
when
it passes
through
wam_, humid
space
An abandoned
masonry
chimney
may be used
as a raceway
%r
properly
insulated
and supported
combustionoair
and vent pipes.
Eacia fhrnace
must
have its own
set of combustion-air
and vent
pipes
and be terminated
individually,
as shown
in Fig. 42.
Other gas appliances
with their own venting
system
may also use
the abandoned
chimney
as a raceway
providing
it is permitted
by
local
code,
the
NFGC
or NSCNGPIC,
and
the vent
or liner
manufacturer's
installation
instn/ctions
(?are must
be taken
to
prevent
the exhaust
gases ti'om one appliance
fiom contaminating
the combustion
air of other
gas appliances.
UNIT
MAY
NOT
OPERATE
Failure
to follow
this caution
may result
in intem_ittent
unit
operation.
When vent pipe is exposed
to temperatures
below
fi'eezing,
such as when it passes
through
an unheated
space
or when a
chimney
is used
as a raceway,
pipe
must
be insulated
as
shown
in Table
8 with Armaflexotype
insulation
UNIT
CORROSION
HAZARD
Excessive
exposure
to
contaminated
comhustion
air
may
result
in sa_bty and perfbrrnance
related
problems.
Combustion
air must
not be
taken
fiom
inside
structure
because
inside
air is frequently
contaminated
by halogens,
which
include
fluorides,
chlorides,
bromides,
and iodides.
These
elements
are found
in aerosols,
detergents,
bleaches,
cleaning
solvents,
salts, air fi'esheners,
adhesives,
paint,
and
other household
products.
Locate
combustionoair
inlet as _r
as possible
fi'om swimming
pool and swimming
pool
pump
hol.lSe,
NOTE:
The minimum
combustionoair
and vent pipe length (each)
for d-_ese hlmaces
is 5 ft. Short pipe lengths
(5°8 ft) may discharge
water
droplets
These
&oplets
may be undesirable,
and a 12-in.
minimum
off'set pipe section
is recommended,
as shown in Fig. 34,
to reduce
excessive
droplets
f_'om exiting
vent pipe outlet.
Combustion-Air
and Vent Pipe Diameter
Determine
combustion-air
and vent pipe diameter.
1. Using
Table
7,
individually
determine
the
smallest
combustionoair
and vent
pipe
diameters
permitted
for each
pipe. Pick the larger
of these
2 pipe diameters
and use this
diameter
for both
combustionoair
and vent pipes.
2. When
installing
vent systems
of short pipe
length,
use
the
smallest
allowable
pipe diameter.
Do not use pipe size greater
than required
becuase
incomplete
combustion,
flame
distur-
bance,
or flame sense lockout
may occur.
NOTE:
Do not count
elbows
or pipe sections
in terminations
or
within
h_mace.
See shaded
areas
in Fig. 36, 37, 38, 39, and 40.
EXAMPLE:
An 080-12
size _hrnace located
in Indianapo-
lis, elevation
650 ft above sea level, could be installed
in an
application
requiring
3 elbows
and 32 ft of vent pipe, along
with
5 elbows
and 34 ft of cornhustionoair
pipe
Table
7
indicates
this application
wo_dd allow a 2oin. diameter
vent
pipe, but require
a 2ol/2
in diameter
combustion
air pipe
(2oin. pipe is good fbr 35 ft with 3 elbows,
but only 30 ft
with 5 elbows).
Therelbre,
2-1/2 in diameter
pipe must be
used for both
vent and combustion-air
pipes
since
larger
required
diameter
must
always
be used
for both
pipes.
If
same
installation
were
in Albuquerque,
elevation
5250 _
above
sea level,
installation
would
require
2ol/2
in. vent
pipe and combustion-air
pipe. At 5001o to 6000o_t eleva-
tion,
2-in. pipe is only good for 17 R with 5 elbows,
and
2-1/2 in. pipe is good fbr 70 R with
5 elbows.
(ombustion-Air
and Vent Pipe Attachment
NOTE:
All pipe joints must be cemented except attachment of
combustion-air
pipe to inlet housing connection, since it may be
necessary to remove pipe _br servicing.
1. Attach combustion=air pipe as follows:
a. Determine location of combustion-air
intake pipe connec-
tion to combustion-air
intake housing as shown in Fig. 33
for application.
b. Reposition combustionoair intake housing plug fitting in
appropriate unused intake housing connection.
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents