Set Gas Input Rate - Carrier AGAGC9PNS01B Installation Instructions Manual

Gas conversion kit, propane to natural condensing (90%+) furnaces 40,000 btuh to 140,000 btuh
Table of Contents

Advertisement

AGAGC9PNS01B Gas Conversion Kit, Propane to Natural: Installation Instructions
Modulating Gas Valve
COMMUNICATION
CONTINUOUS FAN
CONNECTOR
(CF) AIRFLOW
SETUP SWITCHES
MODEL PLUG
CONNECTOR
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
24-V THERMOSTAT
TERMINALS
STATUS AND COMM
LED LIGHTS
3-AMP FUSE
TRANSFORMER 24-VAC
CONNECTIONS
115-VAC (L2) NEUTRAL
CONNECTIONS
PART NUMBER AND
PL1 – LOW VOLTAGE MAIN
DATE CODE WWYY
HARNESS CONNECTOR
SOFTWARE
VERSION
Fig. 23 – Example of Modulating Furnace Control for ECM Blower
1. Turn Setup Switch SW1-2 on furnace control ON, see
2. Jumper R-W/W1 and R-W2 thermostat connections on control.
3. When main burners ignite, confirm inlet gas pressure is between
4.5-in. w.c. and 13.6-in. w.c.
4. Remove jumper across R-W/W1 and R-W2 thermostat connections
to terminate call for heat.
5. Turn furnace gas valve switch to OFF position.
6. Turn gas supply manual shutoff valve to OFF position.
7. Turn off furnace power supply.
8. Remove manometer and on some models remove pressure tap
fitting.
9. On some models, apply pipe dope sparingly to the end of inlet gas
pipe plug and install into unused end of 1/8-in. (3 mm) tee. Use a
small back-up wrench on tee when tightening gas inlet pipe plug.
Or, on some models, tighten set screw on inlet tower pressure tap
with a 3/32-in. hex wrench, see
CHECK FURNACE AND MAKE ADJUSTMENTS
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of leaks to
check all connections. A fire or explosion may result causing property
damage, personal injury or loss of life.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
OUTDOOR
SW4 SETUP
AIR TEMP
SWITCHES
CONNECTOR
PL8 - MODULATING
GAS VALVE
CONNECTOR
TERMINAL (24-VAC
PL3 – ECM BLOWER
PL2 – HOT SURFACE
IGNITER & INDUCER
115-VAC (L1) LINE
MOTOR CONNECTOR
EAC-1 TERMINAL
VOLTAGE CONNECTIONS
(115-VAC 1.0 AMP MAX.)
Motor
Fig.
Fig.
17.
RISQUE D'EXPLOSION ET D'INCENDIE
Le non-respect des avertissements de sécurité pourrait d'entraîner des
blessures graves, la mort ou des dommages matériels.
Ne jamais utiliser une flamme nue por vérifier la présence des fuites de
gaz. Pour la vérification de tous les joints, utiliser plutôt une solution
HUMIDIFIER
savonneuse commerciale fabriquée spécifiquement pur la détection des
0.5 AMP MAX.
fuites de gaz. Un incendie ou une explosion peut entraîner des
dommages matériels, des blessures ou la mort.
1. Be sure main gas and electric supplies to furnace are off.
FLASH
UPGRADE
2. On some models, remove 1/8-in. (3 mm) pipe plug from manifold
CONNECTOR
(FACTORY
ONLY)
pressure tap on the outlet end of gas valve and insert pressure tap.
Or, on some models, loosen the set screw on manifold tower
pressure tap no more than one full turn with the 3/32-in. hex
HARNESS
wrench.
CONNECTOR
3. Attach manometer to manifold pressure tap on gas valve, see
Fig.
11,
Fig.
4. Turn gas supply manual shutoff valve to ON position.
5. Turn furnace gas valve switch to ON position.
6. Check all threaded pipe connections for gas leaks.
L11F061
7. Turn on furnace power supply.
GAS INPUT RATE INFORMATION
23.
See furnace rating plates,see
input rate for natural gas is determined by manifold pressure and orifice
size.
Modulating gas valve must be set for Maximum Heat first and then set
for Minimum heat on Modulating furnaces.
Two-Stage gas valve must be set for High Heat first and then set for Low
Heat on Two-Stage furnaces.
Furnace gas input rate on rating plate is for installations at altitudes up to
2000 ft. (610 M).
In the U.S.A.; the input rating for altitudes above 2000 ft. (610M) must
be reduced by 2 percent for each 1000 ft. (305 M) above sea level.
In Canada; the input rating must be derated by 5 percent for altitudes of
2000 ft. (610 M) to 4500 ft. (1372 M) above sea level.
The Conversion Kit Rating Plate accounts for high altitude derate.

SET GAS INPUT RATE

Single Stage Gas Valve
1. Jumper R and W thermostat connections to call for heat, see
Fig.
20.
2. Check manifold orifices for gas leaks when main burners ignite.
3. Adjust gas manifold pressure, see
4. Remove cap that conceals gas valve regulator adjustment screw.
5. Turn adjusting screw counterclockwise (out) to decrease manifold
pressure or clockwise (in) to increase manifold pressure.
6. Replace gas valve regulator seal cap.
13
AVERTISSEMENT
!
12,
Fig.
13,
Fig.
14, or
Fig.
17.
Fig.
5,
Fig.
6, or
Fig.
Burner Flame
Manifold
Fig. 24 – Burner Flame
Table
4.
7, for input rate. The
Burner
A11461