Carrier 58MXA Installation, Start-Up, And Operating Instructions Manual page 24

Deluxe 4-way multipoise fixed-capacity direct vent condensing gas furnace sizes 040o140, series 170
Table of Contents

Advertisement

TWINNING
AND/OR
BLOWER
OFF-DELAY
COMPONENT
TEST
TERMINAL
24-V
THERMOSTAT
TERMINALS
3-AMP
FUSE
LED
OPERATION
&
DIAGNOSTIC
LIGHT
115-VAC(L2)
CONNECTIONS
HUMIDIFIER
TERMINAL
(24-VAC 05 AMP MAX)
TRANSFORMER
24-VAC
CONNECTIONS
PL1-LOW
VOLTAGE
MAIN
HARNESS
CONNECTOR
Fig. 31--Furnace
Control
A02142
FURNACE
SIZE
040-08
040-12
080-08
060-12
080-16
080-t2
080-16
080-20
100-16
100-20
120-20
140-20
VOLTS--
HERTZ--
PHASE
115-60-1
115-60-1
115-60-1
115-60-1
115-60-1
115-60-1
115-60-1
115-60-1
115-60-1
115-60-1
115-60-1
115-60-1
TaNe 4--Electrical
Data
OPERATING
VOLTAGE
RANGE
Max*
Min*
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
MAX
UNIT
UNIT
AMPS
AMPACBTYt
6.1
8.4
7.3
10.0
6.1
8.4
7.1
9.8
9.5
12.8
7.6
10.4
10.0
13.4
14.1
18.4
10.2
13.5
14.8
19.3
14.6
19.1
14.3
18.8
NIN
WiRE
SIZE
14
14
14
14
14
14
14
12
14
12
12
12
MAX WiRE
LENGTH
(FT)_;
44
37
44
38
29
36
28
31
27
30
30
30
Permissible
limits of voltage
range at which unit will operate satisfactorily.
MAX FUSE
OR CKT BKR
AMPS**
15
15
15
15
15
15
15
20
15
20
20
20
i- Unit ampacity = 125 percent of largest operating
component's
full load amps plus 100 percent of all other potential operating components'
(EAC, humidifier,
etc ) full
load amps
$ Length shown is a measured
1 way along wire path between unit and service panel for maximum
2 percent voltage drop
** Time-delay
type is recommended
_lrnace
casing
in vertical
pipe. (See Fig
320 This allows
proper
drainage
of vent condensate
Combustionoair
and vent pipes
must
terminate
together
in same
atmospheric
pressure
zone,
either
through
roof or sidewall
(roof
termination
preferred),
using
accessoI 7 termination
kit.
See Table 5 tbr required
clearances.
Furnace
combustion-air
and xent pipe
connections
must
be at-
tached
as shown
in Fig. 33. Combustion-air
intake
plug fitdng and
inducer
housing
alternate
_ent cap may need
to be relocated
in
some applications.
NOTE:
Slope combustionoair
and xent pipes down\\ared
toward
furnace
a minimum
of 14 in per linear ft with no sags between
hangers.
24