HP 5800-48G Installation Manual: Removing The Oap Card In The Oap Card Slot; Installing An Oap Card In An Expansion Interface Card Slot

Hp 5820x & 5800 switch series installation guide.
Hide thumbs


Removing the OAP card in the OAP card slot

Do not touch the protection cover marked by the yellow warning label
Underneath this protection cover is a heat radiator. After the OAP card runs for a period of time, this area
can get too hot to touch with bare hands.
Do not touch the surface-mounted components directly with your hands.
To remove the card in the OAP card slot:
Wear an ESD wrist strap and make sure it makes good skin contact and is correctly grounded.
Loosen the captive screws on the OAP card with the Phillips screwdriver until all spring pressure is
released. Do not use excessive force.
Pull the ejector levers outward (see callout 3 in
the guide rails (see callout 4 in
If you do not install a new OAP card in the slot, install a filler panel to prevent dust from entering
the switch and ensure good ventilation in the switch.
Figure 53 Removing the OAP card
(1) OAP card
(3) Pull the ejector levers outward
Installing an OAP card in an expansion interface card slot
Unpack the OAP card and verify that the card can be installed in an expansion interface card slot (see
Follow the procedure described in
interface card slot.
(2) Chassis rear panel
(4) Pull out the OAP card
"Installing an interface
53), and pull out the OAP card slowly along
card" to install the OAP card in an expansion
on the OAP card.