3.2.8 ELECTRICAL CONNECTION

The following instructions do not replace those of the local code.
Installation and verification of this appliance must be done by a qualified
technician.
Installation of the Mini-Caddy wood only furnace requires the use of the ``fan limit
assembly for wood only`` option (PA00500) which must be purchased separately.
This option includes the fan limit control; install the fan limit control on the back of
the furnace, next to the flue outlet where there are holes to insert the probe and
secure the assembly. It is normal that the fan limit control is not vertical once
installed.
Plastic grummets are installed on the upper edge of the blower box through
which the blower cable (prewired 14-3 BX) will run before reaching the junction
box located next to the blower where it will be connected.
The low voltage control circuit will be fed from the transformer attached to the
junction box of the fan limit assembly and the 120 volts circuit from the house
electrical entrance will also be connected to that junction box as per the wiring
diagram (31.2.13).
ATTENTION
USE WIRES SUITABLE FOR 75° C OR MORE.

3.2.9 THERMOSTAT

The thermostat must be installed on an inside wall in a location where it is less
likely to be affected by the draft coming from an air outlet. It must be installed at
a minimum of 55 inches above the floor

3.2.10 FAN LIMIT CONTROL

The fan limit control settings may need to be adjusted depending on the
installation but they are set at 110 °F (fan off) and 150 °F. (Fan on) at the factory
and these settings will work best in most installations.
The adjustment of all controls must be performed by a qualified technician. The
controls setting and the blower speed must conform to the recommendations of
the "Warm Air Heating and Air Conditioning National Association".
For
continuous operation of the blower, use the switch located below the fan limit
39