Flue And Barometric Draft Control Connection; Damper - PSG MINI-CADDY PF01301 Installation And Operating Instructions Manual

Table of Contents

Advertisement

2.10 FLUE AND BAROMETRIC DRAFT CONTROL CONNECTION

BEFORE CONNECTING THE STOVE PIPE, MAKE SURE YOU HAVE
REMOVED THE SCRAPER FROM THE FLUE PIPE.
For a proper installation, follow the advice below:
1- All the exhaust pipe joints must be secured with three screws.
Make sure that each screw goes through the inner wall of both connectors
(male and female). See pictures below showing a male-female coupling.
PROPER INSTALLATION
2- A minimum rise of ¼" per horizontal foot must be respected.

2.11 DAMPER

The barometric damper must be adjusted so that the maximum draft measured at
the furnace outlet is limited to -0.06 in. w.c. However, the minimum draft to be
respected at all times is -0.04 in. w.c. in the evacuation pipe.
DRAFT HIGHER THAN -0.06" W.C. MAY CAUSE AN UNCONTROLLABLE
FIRE.
ATTENTION
CAUSES
RESTRICTION
IMPROPER INSTALLATION
WARNING
11