9.8. FLUE AND BAROMETRIC DRAFT CONTROL CONNECTION

Before connecting the stove pipe, make sure you have removed any accessory from the flue
pipe such as the scraper, shovel, and the poker.
The flue outlet on the Max Caddy furnace is 6" in diameter and the wood only or wood/electric models may be installed
with a 6" chimney approved for use with wood burning heating appliances (2100°F). However, it is mandatory to use a
7" diameter chimney if the retrofit to a wood/oil configuration is probable. In that case, a 6" to 7" reducer must be
installed at the flue outlet of the furnace. If the draft exceeds 0.06 IN.W.C., a barometric control must installed. Never
install a manual damper. Secure the exhaust pipe to the flue adapter with three screws.
FLUE
ADAPTER
WOOD ONLY
For a proper installation, follow the advice below:
All the exhaust pipe joints must be secured with three screws.
Make sure that each screw goes through the inner wall of both connectors (male and female). See pictures below
showing a male-female coupling.
A minimum rise of ¼" per horizontal foot must be respected.
PROPER INSTALLATION
24
Diameter 6"
Unit oil
OIL UNIT'S
UTLET
Max Caddy pipe
Reducer 7" to 6"
IMPROPER INSTALLATION
CAUSES RESTRICTION
Diameter 7"
WOOD/OIL