[24] Protection functions [3/3]
Communi
Title
cation
Function
No.
0637
PTC1 thermal selection
0638
PTC2 thermal selection
Braking resistance overload time
0639
(10 times of rated torque)
Step-out detection current level
0640
(for PM motors)
Step-out detection time (for PM
0641
motors)
Brake-equipped motor restart
0643
condition selection
Control power supply backup
0647
option failure monitoring
*1: ⇒ For details, refer to Instruction Manual (E6581339) specified in Section 6.42.
[25] Override
Communi
Title
cation
Function
No.
0660
Override addition input selection
Override multiplication input
0661
selection
Logic output/pulse output
0669
selection (OUT1)
0670
AM terminal meter selection
This parameter moves to a fundamental parameter.
*1: ⇒ For the adjustment range, see the table on page K-39.
Adjustment range
0:Deselect
1:Select
0:Deselect
1:Select
0.1~600.0 sec.
10~150
0.0:Not detect
0.1~25.0
0:Default (no waiting time for frequencies of 10Hz
and less)
1:Conditional (no waiting time for frequencies of
20Hz and less)
0:Control power supply not backed up
1:Control power supply backed up (alarm in the
event of a failure)
2:Control power supply backed up (tripping in the
event of a failure)
Adjustment range
0:Disabled
1:VI/II (voltage/current input)
2:RR/S4 (potentiometer/voltage input)
3:RX (voltage input)
4:Operation panel input enabled (including
LED/LCD option input)
5:2-wire RS485 input enabled
6:4-wire RS485 input enabled
7:Communications option input enabled
8:Optional AI1 (differential current input)
9:Optional AI2 (voltage/current input)
10:UP/DOWN frequency
11:Optional RP pulse input
12:Optional high-speed pulse input
13:Optional binary/BCD input
0:Disabled, 1:VI/II, 2:RR/S4, 3:RX, 4:,
5:Optional AI1
0:Logic output
1:Pulse output
0~64 *1
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Minimum
Vector control
setting unit
Default
Write during
Speed
(Panel/Communi
setting
running
control
cation)
1/1
0
Disabled
●/●
1/1
0
Disabled
●/●
0.1/0.1
5.0
Disabled
●/●
1/1
100
Disabled
-
0.1/0.1
0.0
Disabled
-
1/1
0
Disabled
●/●
1/1
0
Disabled
●/●
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Minimum
Vector control
setting unit
Default
Write during
Speed
(Panel/Communi
setting
running
control
cation)
1/1
0
Enabled
●/●
1/1
0
Enabled
●/●
1/1
0
Disabled
●/●
1/1
2
Enabled
●/●
PM
Torque
V/f Constant Reference
control
control
●/●
●
●
*1
●/●
●
●
*1
●/●
●
●
5. 19
-
●
-
6. 29
-
●
-
6. 29
●/●
●
●
6. 33. 23
●/●
●
●
6. 33. 24
PM
V/f Constant Reference
Torque
control
control
-
●
●
6. 34
-
●
●
6. 34
●/●
●
●
6. 35. 1
●/●
●
●
5. 16