Fine Adjustment Of Frequency Setting Signal; Operating A Synchronous Motor - Toshiba TOSVERT VF-AS1 Instruction Manual

High-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

6.28

Fine adjustment of frequency setting signal

 : VI/II input bias
 : VI/II input gain
 : RR/S4 input bias
 : RR/S4 input gain
 : RX input bias
• Function
These parameters are used to fine adjust the relation between the frequency setting signal input through
the analog input terminal and the output frequency.
Use these parameters to make fine adjustments after making rough adjustments using the parameters
~.
The figure below shows the characteristic of the frequency setting signal input through the analog input terminal and
that of the output frequency.
Output frequency [Hz]
Maximum frequency
6
, 
, 

Bias adjustment of analog input terminals (, , , , )
To give leeway, the inverter is factory-adjusted by default so that it will not produce an output until a certain amount
of voltage is applied to the analog input terminals.
To reduce leeway, decrease the bias of the analog terminal in use.
Note that specifying a too large value may cause an output frequency to be output, even though the operation
frequency is 0 (zero) Hz.
Gain adjustment of analog input terminals (, , , , )
The inverter is factory-adjusted by default so that the operation frequency can reach the maximum frequency, even
though the voltage and current to the analog input terminals are below the maximum levels.
To make an adjustment so that the frequency reaches its peak value at the maximum voltage and current, decrease
the gain of the analog terminal in use.
Note that specifying a too small value may cause the operation frequency not to reach the maximum frequency, even
though the maximum voltage and current are applied.
6.29

Operating a synchronous motor

 ,  : PM motor constant 1
 ,  : Step-out detection current level/ detection time
This parameter is used only when the inverter is used with a synchronous motor. If you intend to use your inverter with
a synchronous motor, contact us at the your supplier.
Large
Small
0
0
0V
4mA
Frequency setting signal (Analog input terminal)
F-50
 : RX input gain
 : Optional AI1 input bias
 : Optional AI1 input gain
 : Optional AI2 input bias
 : Optional AI2 input gain
Large
, , 
, 
Small
Factory default setting
100
10Vdc
20mAdc
E6581445