6.33.8 Control mode for low current
: Low current detection hysteresis width
: Low current trip selection
: Low current detection current
: Low current detection time
• Function
If the current is lower than level and passes for a time longer than , the inverter trips.
Trip information is displayed as "."
=: No tripping (Failure signal FL deactivated).
=: The inverter will trip (the failure signal FL will be activated) if a current below the current set with
Title
<Example of operation>
6
Output terminal function: 26 (UC) Low current detection
= (No trip)
Ex.) When outputting low current detection signals through output terminal OUT1
Title
Note:To put out signals to the terminal OUT2, select the parameter .
When = (tripping), the inverter will trip if low current lasts for the period of time set with .
After tripping, the low current signal remains ON.
A low current alarm can be put out by setting the output terminal function selection parameter.
flows for the period of time specified with .
Function
Low current detection hysteresis width
Low current trip selection
Low current detection current
Low current detection time
Function
Output terminal function selection 1(OUT1)
Low current
signal output
Output current [%]
+
Adjustment range
~ %
: No trip
:Trip
~ %
~ sec.
Adjustment range
~
less than
F-60
E6581445
Default setting
Example of setting
ON
OFF
OFF
Time [sec]