Toshiba TOSVERT VF-AS1 Instruction Manual page 219

High-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

(Continued)
Commun
ication
Item displayed
No.
[Note 5]
FE10
Past trip 1
[Note 5]
FE11
Past trip 2
[Note 5]
FE12
Past trip 3
[Note 5]
FE13
Past trip 4
Part replacement
[Note 6]
FE79
alarm information
Cumulative
[Note 7]
FE14
operation time
Default display
mode
Note 1: Press the
Note 2: Contents of status indications of *1, *2, *3, *4, *5, *6, *7, *8, and *9 can be selected from 44 kinds of
information.
Contents of status indications that are set up at  (standard monitor display selection) and
~ (status monitor 1 to 8 display selection) are displayed.
Unit of current and voltage indications can be changed from % to A (ampere)/V (volt) and vice versa
respectively. ⇒ Refer to Section 5.15.
Note 3: Indicated input voltage is DC voltage just after input voltage is rectified multiplied by 1 2 .
Note 4: The number of bars displayed varies depending on the setting of  (logic output/pulse train output
selection.)
The bar representing the OUT1 terminal is displayed only when logic output function is assigned to it.
If  =  : The bar representing OUT1 is displayed.
If  =  : The bar representing OUT1 is not displayed.
Note 5: Past rip records are displayed in the following sequence: 1 (latest trip record) ⇔ 2 ⇔ 3 ⇔ 4 (oldest trip record).
If there is no trip record,  is displayed.
Details on past trip record 1, 2, 3 or 4 can be displayed by pressing the
is displayed. ⇒ For more details, refer to Section 8.2.2.
Note 6: The part replacement alarm is displayed based on the value calculated from the annual average ambient
temperature, operation time and load current specified using  .
Use this alarm as a guide only, since it is based on a rough estimation.
Note 7: The cumulative operation time increments only when the machine is in operation.
Key
LED
operated
display
Past trip 1 (displayed alternately at 0.5-sec. intervals)
⇔
 ⇔
Past trip 2 (displayed alternately at 0.5-sec. intervals)
⇔
Past trip 3 (displayed alternately at 0.5-sec. intervals)
⇔ Past trip 4 (displayed alternately at 0.5-sec. intervals)
The ON/OFF status of each of the cooling fan, circuit
board capacitor, main circuit capacitor or part
replacement alarm of cumulative operation time is
displayed in bits.
ON:
OFF:

The cumulative operation time is displayed.
 
(Indication of 0.1 represents 10 hours.)
MODE
The operation frequency is displayed (during operation).

[Note 1]
keys to change items displayed in the status monitor mode.
H-3
Description

Cooling fan
Cumulative
operation time
Control circuit board
capacitor
Main circuit capacitor
ENT key when past trip 1, 2, 3 or 4
E6581445
8

Advertisement

Table of Contents
loading