2.3
Programming with a Computer (Network Setup)
Before proceeding with any of the programming steps in this section, install the 1812 Management
software on the computer that will be used for this purpose. Be sure that the computer has a network
card installed, or a modem installed in it (or connected to it) depending on which connection method
will be used.
Once the software is installed and the 1812 is connected, refer to the software
programming steps and help screen instructions to proceed with the programming steps in this
section.
Be sure that SW1 is in the ON position (MODEM/TCP ENB) on the interface board.
Reboot: If a programming step calls for a reboot, follow the programming steps in 2.3.1. If you are
performing several programming steps that call for a reboot, complete all of those steps first, then
perform the reboot sequence in 2.3.1.
2.3.1 Enable / Disable TCP / IP Support – System Reboot
Default value is: 0 (Disabled)
This programming sequence enables or disables the support for TCP / IP. It will also cause an
automatic reboot of the 1812 two seconds after the programming sequence is completed. For this
reason, perform this step after all other network setup programming sequences have been
completed (2.3.2 through 2.3.5) or whenever an individual network programming step is
performed.
1. Press * 5 0 and enter the MASTER CODE. [* 5 0 _ _ _ _ (beep)]
2. Press 0 * to disable OR press 1 * to enable. [ _ * (beep)]
3. The system will reboot automatically.
Once the 1812 is connected, the green LED on the RJ-45 jack on the interface board should light
indicating that a good wire connection has been made. The LAN DOWN LED should go off after a
few seconds if all previous programming steps have been completed and programmed successfully.
2.3.2 Set the 1812 IP Address (reboot required)
Default value is: 192.168.001.030
This must be set to the same address that was programmed in the software. A valid value for any of
the three digit numbers in this sequence is 000 to 255.
1. Press * 5 1 and enter the MASTER CODE. [* 5 1 _ _ _ _ (beep)]
2. Enter the IP address. Use the * key to enter the "dot."
[ _ _ _ * (beep) _ _ _ * (beep) _ _ _ * (beep) _ _ _ * (beep)]
3. Press 0 # TOGETHER to end. [0 # (beeeeeep)]