X530 Neutral Point Grounding - Siemens SINAMICS S120 Manual

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

2.6.3.5

X530 neutral point grounding

Table 2- 25
The Voltage Sensing Module is supplied with inserted jumper. When delivered, the neutral
point is connected to the protective conductor via the connector jumper. A current flows to
PE as a result of the voltage to be measured. This connection is removed by removing the
connector jumper. The measurement is then electrically isolated.
Figure 2-16
Chassis power units
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
Neutral point grounding X530
Terminal
Designation
1
Neutral point of the voltage
sensing
2
Ground potential
Internal circuit of the VSM10 Voltage Sensing Module
Line-side power components
2.6 Active Interface Modules
Technical data
Jumper inserted: Grounded
measurement
Jumper not inserted: isolated
measurement
71