Siemens SINAMICS S120 Manual page 271

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cable cross-sections
Table 6- 18
dV/dt filter plus voltage
6SL3000-2DE32-6AA0
6SL3000-2DE35-0AA0
6SL3000-2DE38-4AA0
6SL3000-2DE41-4AA0
6SL3000-2DH31-0AA0
6SL3000-2DH31-5AA0
6SL3000-2DH32-2AA0
6SL3000-2DH33-3AA0
6SL3000-2DH34-1AA0
6SL3000-2DH35-8AA0
6SL3000-2DH38-1AA0
6SL3000-2DH41-3AA0
Risk of fire and damage to equipment due to short-circuit / ground fault
The cables to the DC link of the Motor Modules must be routed so that a ground fault or
short-circuit can be ruled out. A ground fault can result in fire with smoke.
• Protect the cables from mechanical damage.
• Comply with local installation regulations that enable this fault to be ruled out.
In addition, apply one of the following measures:
• Use cables with double insulation.
• Maintain adequate clearance, using spacers, for example.
• Route the cables in separate cable ducts or pipes.
Note
Maximum cable lengths
The connections should be kept as short as possible.
The maximum cable length for the specified connections is 5 m in each case.
Chassis power units
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
Cable cross-sections for connections between the dV/dt filter plus voltage peak limiter
and Motor Module
peak limiter
WARNING
Connection to the DC link
(DCPS/DCNS)
[mm²]
380 ... 480 V line voltage
35
70
2 x 50
2 x 120
500 ... 690 V line voltage
16
16
70
70
120
120
2 x 70
2 x 120
Motor-side power components
6.3 dv/dt filter plus Voltage Peak Limiter
Connection between dV/dt reactor and
voltage peak limiter
(1U2, 1V2, 1W2) [mm²]
10
16
50
120
6
6
16
16
35
35
70
120
269