X41 Ep Terminal / Temperature Sensor Connection - Siemens SINAMICS S120 Manual

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.3.6

X41 EP terminal / temperature sensor connection

Table 4- 5
Terminal strip X41
Terminal
1
2
3
4
Max. connectable cross-section 1.5 mm
Electrical shock hazard
Only temperature sensors that meet the safety isolation specifications stipulated in
EN 61800-5-1 may be connected to terminals "+Temp" and "-Temp". If safe electrical
separation cannot be guaranteed (for linear motors or third-party motors, for example), a
Sensor Module External (SME120 or SME125) must be used.
If these instructions are not complied with, there is a risk of electric shock!
Note
Connectable sensor
The following probes can be connected to the temperature sensor connection:
KTY84-1C130 / PTC / PT100.
NOTICE
Use shielded cables
The temperature sensor connection must be shielded. The shielding must be attached to
the shield support of the Motor Module.
Note
KTY temperature sensor connected with the correct polarity
The KTY temperature sensor must be connected with the correct polarity.
If the polarity is reversed, the sensor will not be able to detect if the motor overheats.
Chassis power units
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
Function
EP M1 (Enable Pulses)
EP +24 V (Enable Pulses)
- Temp
+ Temp
2
DANGER
Technical specifications
Supply voltage: 24 VDC (20.4 ... 28.8 V)
Current consumption: 10 mA
Signal propagation delay times:
L → H 100 μs
H → L: 1000 μs
The pulse inhibit function is only available when Safety
Integrated Basic Functions are enabled.
Temperature sensor connection KTY84-1C130/PTC /
PT100
Motor Modules
4.3 Interface description
187