Motor Modules
4.6 Technical specifications
Order number
Max. conductor cross-sections
- DC-link connection (DCP, DCN)
- Motor connection (U2, V2, W2)
- PE connection PE1
- PE connection PE2
Max. motor cable length
- Shielded
- Unshielded
Degree of protection
Dimensions
- Width
- Height
- Depth
Frame size
Weight
Rated power of a typical 6-pole standard induction motor based on I
1)
Rated power of a typical 6-pole standard induction motor based on I
2)
Including overshoot capability
3)
The specified power loss is the maximum value at 100% capacity utilization. The value in normal operation is lower.
4)
208
6SL3320–
1TG34–1AA3
mm²
Busbar
mm²
4 x 240
mm²
1 x 240
mm²
2 x 240
m
300
m
450
IP00
mm
503
mm
1475
mm
547
HX
kg
290
or I
L
or I
L
1TG34–7AA3
1TG35–8AA3
Busbar
Busbar
4 x 240
4 x 240
1 x 240
1 x 240
2 x 240
2 x 240
300
300
450
450
IP00
IP00
503
503
1475
1475
547
547
HX
HX
290
290
at 3 AC 500 V or 690 V 50 Hz.
H
at 3 AC 575 V 60 Hz.
H
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
1TG37–4AA3
Busbar
6 x 240
1 x 240
3 x 240
300
450
IP00
704
1475
550
JX
450