Line-side power components
2.2 Line filters for Basic Line Modules
Table 2- 4
Technical data of line filters for Basic Line Modules, 3 AC 500 ... 690 V, Part 1
Order number
Suitable for
Basic Line Module
Rated power of the Basic
Line Module
Rated voltage
Rated current
Power loss
Line supply/load connection
L1, L2, L3 / L1', L2', L3'
PE connection
Degree of protection
Dimensions
Width
Height
Depth
Weight
Table 2- 5
Technical data of line filters for Basic Line Modules, 3 AC 500 ... 690 V, Part 2
Order number
Suitable for
Basic Line Module
Rated power of the Basic
Line Module
Rated voltage
Rated current
Power loss
Line supply/load connection
L1, L2, L3 / L1', L2', L3'
PE connection
Degree of protection
Dimensions
Width
Height
Depth
Weight
42
6SL3000-
0BG34-4AA0
6SL3330-
1TG33-3AAx
kW
250
V
A
440
kW
0.047
M10 connecting
lugs
M8
IP00
mm
360
mm
240
mm
116
kg
12.3
6SL3000-
0BG41-2AA0
6SL3330-
1TG41-4AAx
kW
1100
V
A
1200
kW
0.119
M12 connecting
lugs
M10
IP00
mm
425
mm
265
mm
145
kg
25.8
0BG34-4AA0
1TG34-3AAx
355
3 AC 500 -10% (-15% < 1 min) ... 3 AC 690 +10%
440
0.047
M10 connecting
lugs
M8
IP00
360
240
116
12.3
0BG41-6AA0
1TG41-8AAx
1500
3 AC 500 -10% (-15% < 1 min) ... 3 AC 690 +10%
1600
0.182
M12 connecting
lugs
M10
IP00
505
265
145
28.8
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
0BG36-0AA0
0BG41-2AA0
1TG36-8AAx
1TG41-1AAx
560
600
0.053
M10 connecting
M12 connecting
lugs
M10
IP00
400
265
140
19.0
Chassis power units
900
1200
0.119
lugs
M10
IP00
425
265
145
25.8