Line Modules
3.3 Smart Line Modules
Order number
Dimensions
- Width
- Height
- Depth
Frame size
Weight, approx.
Recommended fuse
2)
- Number (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Minimum short-circuit current
The specified power loss is the maximum value at 100% capacity utilization. The value in normal operation is lower.
1)
To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
2)
Current required for reliable triggering of the protective devices.
3)

Overload capability

The Smart Line Modules have an overload reserve.
The criterion for overload is that the Smart Line Module is operated with its base load current
before and after the overload occurs (a load duration of 300 s is used as a basis here).
146
6SL3330–
mm
mm
mm
kg
A
3)
6TG35–5AA3
6TG38–8AA3
310
503
1420
1475
550
550
GX
HX
150
294
3NE1435-2
3NE1448-2
1
1
560
850
3
3
6200
10500
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
6TG41–2AA3
6TG41–7AA3
704
704
1480
1480
550
550
JX
JX
458
458
3NE1435-2
3NE1448-2
2
2
560
850
3
3
12400
21000