Siemens SINAMICS S120 Manual page 88

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
2.6 Active Interface Modules
Table 2- 30
Technical data for Active Interface Modules, 3 AC 500 V ... 690 V
Order number
Suitable for Active Line Module
Rated power of
Active Line Module
Rated current
Supply voltages
- Line voltage
- Line frequency
- Electronic power supply
- Fan supply voltage
DC-link capacitance
of the drive line-up, max.
Current consumption
- Electronics current consumption
(24 VDC)
- Fan supply, 2 AC 230 V,
- Max. precharging current (max. 3 s)
Bypass contactor
2)
Max. ambient temperature
- Without derating
- With derating
Power loss, max.
1)
- At 50 Hz 690 V
- At 60 Hz 575 V
Cooling air requirement
Line/load connection
L1, L2, L3 / U2, V2, W2
PE connection
Line/load connection
- Line connection (L1, L2, L3)
- Load connection (U2, V2, W2)
- PE connection
Degree of protection
Dimensions
- Width
- Height
- Depth
Frame size
Weight
The specified power loss is the maximum value at 100% capacity utilization. The value in normal operation is lower.
1)
Bypass contactor is not included, must be provided separately.
2)
The circuit breaker is controlled by the sequential control system of the Active Line Module and must not be switched on
3)
manually. It is therefore recommended that the circuit breaker be equipped with the 3WL9111-0BA21-0AA0 locking set.
86
6SL3300–
7TG35–8AA0
6SL3330-
7TG35-8AAx
kW
560
A
575
V
3 AC 500 –10% (-15% < 1 min) ... 3 AC 690 +10%
ACrms
Hz
V
DC
V
AC
µF
59200
A
0.17
A
4.6
A
141
3RT1476-
6AP36
° C
40
° C
55
kW
6.8
kW
6.8
m
/s
0.40
3
M12
M12 screw
mm²
4 x 240
mm²
4 x 240
mm²
2 x 240
IP00
mm
305
mm
1750
mm
544
HI
kg
390
7TG37–4AA0
7TG41–3AA0
7TG37-4AAx
7TG41-0AAx
800
1100
735
1025
47 ... 63 Hz
24 (20.4 ... 28.8)
230 (195.5 ... 264.5)
153600
153600
0.17
0.17
4.9
4.9
141
141
3RT1476-
3WL1212-
6AP36 (3 x)
4BB34-4AN2-Z
Z=C22
3)
40
40
55
55
9.0
9.2
9.0
9.2
0.40
0.40
Flat connector for screw
M12
M12
M12 screw
M12 screw
6 x 240
6 x 240
6 x 240
6 x 240
4 x 240
4 x 240
IP00
IP00
505
505
1750
1750
544
544
JI
JI
620
620
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
7TG41–3AA0
7TG41-3AAx
1400
1270
153600
0.17
4.9
141
3WL1216-
4BB34-4AN2-Z
Z=C22
3)
40
55
9.6
9.6
0.40
M12
M12 screw
6 x 240
6 x 240
4 x 240
IP00
505
1750
544
JI
620
Chassis power units

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents