Table 3- 15
Technical data for Basic Line Modules, 500 V ... 690 V 3 AC, Part 1
Order number
Rated power
- For I
(50 Hz, 690 V)
n_DC
- For I
(50 Hz, 690 V)
H_DC
- For I
(50 Hz, 500 V)
n_DC
- For I
(50 Hz, 500 V)
H_DC
- For I
(60 Hz, 575 V)
n_DC
- For I
(60 Hz, 575 V)
H_DC
DC-link current
- Rated current I
n_DC
- Base load current I
H_DC
- Maximum current I
max_DC
Input current
- Rated current I
n_E
- Maximum current I
max_E
- Maximum precharging current (max. 3 s)
Supply voltages
- Line voltage
- Line frequency
- Electronic power supply
- Fan supply voltage
- DC-link voltage
Current consumption
- Electronics current consumption
(24 VDC)
- Fan power consumption
(230 VAC)
Max. ambient temperature
- Without derating
- With derating
DC-link capacitance
- Basic Line Module
- Drive line-up, max.
Power loss, max.
1)
- At 50 Hz 690 V
- At 60 Hz 575 V
Cooling air requirement
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Line/load connection
Max. connection cross-sections
- Line connection (U1, V1, W1)
- DC-link connection (DCP, DCN)
- PE connection
Max. cable length
(total of all motor cables and DC link)
- Shielded
- Unshielded
Degree of protection
Chassis power units
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
6SL3330–
1TG33–0AA3
kW
250
kW
195
kW
175
165
kW
HP
250
HP
200
A
300
A
234
A
450
A
260
A
390
A
internal
V
3 AC 500 -10% (-15% < 1 min) ... 3 AC 690 +10%
ACrms
Hz
V
DC
V
AC
V
1.35 x U
DC
A
1.1
A
1.1
° C
40
° C
55
µF
3200
µF
25600
kW
1.5
kW
1.5
m
/s
0.17
3
dB(A)
66 / 68
M10
mm²
2 x 240
mm²
2 x 240
mm²
2 x 240
m
1500
m
2250
IP00
3.2 Basic Line Modules
1TG34–3AA3
1TG36–8AA3
355
560
280
440
250
390
235
365
350
600
300
450
430
680
335
530
645
1020
375
575
563
863
internal
internal
47 ... 63 Hz
24 (20.4 ... 28.8)
230 (195.5 ... 264.5)
(partial load) / 1.32 x U
line
1.1
1.1
1.1
1.1
40
40
55
55
4800
7300
38400
58400
2.1
3.0
2.1
3.0
0.17
0.17
66 / 68
66 / 68
Flat connector for screw
M10
M10
2 x 240
2 x 240
2 x 240
2 x 240
2 x 240
2 x 240
1500
1500
2250
2250
IP00
IP00
Line Modules
1TG41–1AA3
900
710
635
595
900
800
1100
858
1650
925
1388
internal
(full load)
line
1.1
4.5
40
55
11600
92800
5.4
5.4
0.36
71 / 73
M12
6 x 185
6 x 185
4 x 240
2250
3375
IP00
113