Line Reactors For Smart Line Modules; Description; Safety Information - Siemens SINAMICS S120 Manual

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components

2.5 Line reactors for Smart Line Modules

2.5
Line reactors for Smart Line Modules
2.5.1

Description

Line reactors limit low-frequency line harmonics and reduce the load on the semiconductors
in the Smart Line Modules. For this reason, line reactors must always be provided when
Smart Line Modules are used.
2.5.2

Safety information

NOTICE
Maintain ventilation clearances
The 100 mm ventilation clearances above and to the side of the components must be
observed.
Note
Cable lengths
The connecting cables to the Line Module must be kept as short as possible (max. 5 m).
NOTICE
Use only approved line reactors
When using line reactors that have not been approved by SIEMENS for SINAMICS, the
following can occur:
• The Smart Line Modules may become damaged/faulty.
• Line harmonics may interfere with or damage other loads connected to the same line
Hot surfaces
The surface temperature of the line reactors can exceed 80° C.
54
supply.
CAUTION
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
Chassis power units

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents